Brochure

Table Of Contents
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2014 Johnson Controls, Inc.
www.johnsoncontrols.com
V–262
M9000 Electrically Actuated, Standard-Pressure, Standard-Temperature, Two-Way
Butterfly Valves (with Weather Shield) (Continued)
Butterfly Valves and Actuators
Technical Specifications
Two-Way — Non-Spring Return
On/Off (Floating) Control 0 to 10 VDC Proportional Control
M91xx-AGA-2
without switches
M91xx-AGC-2
with 2 Switches
M91xx-GGA-2
without switches
M91xx-GGC-2
with 2 Switches
VWN020HB 2 144 84 175
VWN020HB+916AGA VWN020HB+916AGC VWN020HB+916GGA VWN020HB+916GGC
VWN025HB 2-1/2 282 163 175
VWN025HB+916AGA VWN025HB+916AGC VWN025HB+916GGA VWN025HB+916GGC
VWN030HB 3 461 267 175
VWN030HB+916AGA VWN030HB+916AGC VWN030HB+916GGA VWN030HB+916GGC
VWN040HB 4 841 496 175
VWN040HB+924AGA VWN040HB+924AGC VWN040HB+924GGA VWN040HB+924GGC
VWN050LB 5 1376 775 50
VWN050LB+924AGA VWN050LB+924AGC VWN050LB+924GGA VWN050LB+924GGC
VWN050HB 5 1376 775 175
VWN050HB2924AGA
2
VWN050HB2924AGC
2
VWN050HB2924GGA
2
VWN050HB2924GGC
2
VWN060LB 6 1850 1025 50 VWN060LB2924AGA
2
VWN060LB2924AGC
2
VWN060LB2924GGA
2
VWN060LB2924GGC
2
1. Valves rated for 175 psig closeoff have 75 psig maximum dead-end service rating. Valves rated for 50 psig closeoff are not rated for dead-end service.
2. Valve assemblies have two actuators mounted in tandem.
M9000 Electrically Actuated, Standard-Pressure, Standard-Temperature, Two-Way Butterfly Valves (with Weather Shield)
1
1. Refer to the VF Series Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin (LIT-977205P) for actuator specifications.
Service Hot, Chilled, or Condenser Water, and 50/50 Glycol Solutions (Not Designed for Use in Steam Applications)
Body Styles and Sizes Two-Way, 2 through 6 in., Fully Lugged
Fluid Temperature Limits -40°F to 250°F (-40°C to 121°C)
Body Pressure Rating 175 psig
Maximum Fluid Velocity 30 ft/second (9 m/second)
Rangeability Refer to the VF Series Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin (LIT-977205P).
Leakage Bubble Tight
Flow Characteristics Modified Equal Percentage
Materials Body Cast Iron ASTM A126 Class B
Tee (Three-Way
Valves Only)
Cast Iron
Disc Ductile Iron, Nylon 11 Coated, ASTM A536 Gr 65-45-12
Seat Ethylene Propylene Diene Monomer (EPDM)
Stem 416 Stainless Steel
Ambient Temperature
Limits
Storage -20 to 150°F (-29 to 66°C), Preferably 40 to 85°F (4 to 29°C)
Operating Spring-Return Actuator: -40 to 131°F (-40 to 55°C)
Non-Spring-Return Actuator: -4 to 122°F (-20 to 50°C)
Weather Shield Rating National Electrical Manufacturers’ Association (NEMA) 4
M9000 Electrically Actuated, Standard-Pressure, Standard-Temperature, Two-Way Butterfly Valves (with Weather Shield)
(Part 2 of 2)
Valve Code
Number
Size,
in.
Cv
at 90°
Cv
at 70°
Closeoff
Pressure,
psig
1
Two-Way Valve with M9000 Series Electric Actuator (with Weather Shield)
Spring Open Spring Closed Spring Open Spring Closed
Pneumatic Damper
Actuators
Buttery Valves and
Actuators