Brochure

Table Of Contents
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2014 Johnson Controls, Inc.
www.johnsoncontrols.com
V–239
VG2000 Series Pneumatic Cast Iron Flanged Globe Valves (Continued)
Flanged Globe or Ball Valves and Actuators
Selection Charts
Two-Way Normally Open Pneumatic Cast Iron Flanged Globe Valves
Spring Range 3 to 7 psig 4 to 8 psig 9 to 13 psig
Valve
Code Number
Size, in. Cv Closeoff
psig
Code Number Closeoff
psig
Code Number Closeoff
psig
Code Number
With MP82 Series Actuators — 25 sq. in. Effective Diaphragm Area
VG2231TL 2-1/2 51 53 VG2231TL+823C00 49 VG2231TL+823D00 28 VG2231TL+823E00
VG2231UL 3 83 37 VG2231UL+823C00 34 VG2231UL+823D00 19 VG2231UL+823E00
With MP84 Series Actuators — 50 sq. in. Effective Diaphragm Area
VG2231TM 2-1/2 51 109 VG2231TM+843C00 100 VG2231TM+843D00 58 VG2231TM+843E00
VG2231UM 3 83 75 VG2231UM+845C00 70 VG2231UM+845D00 40 VG2231UM+845E00
VG2231VM 4 150 42 VG2231VM+845C00 39 VG2231VM+845D00 23 VG2231VM+845E00
With MP86 Series Actuators — 100 sq. in. Effective Diaphragm Area
VG2231UN 3 83 152 VG2231UN+865C00 140 VG2231UN+865D00 81 VG2231UN+865E00
VG2231VN 4 150 86 VG2231VN+865C00 79 VG2231VN+865D00 46 VG2231VN+865E00
VG2231WN 5 240 55 VG2231WN+867C00 51 VG2231WN+867D00 29 VG2231WN+867E00
VG2231YN 6 350 38 VG2231YN+867C00 35 VG2231YN+867D00 20 VG2231YN+867E00
Two-Way Normally Closed Pneumatic Cast Iron Flanged Globe Valves
Spring Range 3 to 7 psig 4 to 8 psig 9 to 13 psig
Valve
Code Number
Size, in. Cv Closeoff
psig
Code Number Closeoff
psig
Code Number Closeoff
psig
Code Number
With MP84 Series Actuators — 50 sq. in. Effective Diaphragm Area
VG2431TM 2-1/2 54 24 VG2431TM+843C00 32 VG2431TM+843D00 75 VG2431TM+843E00
VG2431UM 3 83 17 VG2431UM+845C00 22 VG2431UM+845D00 52 VG2431UM+845E00
VG2431VM 4 150 9 VG2431VM+845C00 13 VG2431VM+845D00 29 VG2431VM+845E00
With MP86 Series Actuators — 100 sq. in. Effective Diaphragm Area
VG2431UN 3 83 34 VG2431UN+865C00 46 VG2431UN+865D00 105 VG2431UN+865E00
VG2431VN 4 150 19 VG2431VN+865C00 26 VG2431VN+865D00 59 VG2431VN+865E00
VG2431WN 5 237 12 VG2431WN+867C00 17 VG2431WN+867D00 38 VG2431WN+867E00
VG2431YN 6 344 9 VG2431YN+867C00 11 VG2431YN+867D00 26 VG2431YN+867E00
Three-Way Mixing Pneumatic Cast Iron Flanged Globe Valves
Spring Range 3 to 7 psig 4 to 8 psig 9 to 13 psig
Valve
Code Number
Size, in. Cv Closeoff
psig
Code Number Closeoff
psig
Code Number Closeoff
psig
Code Number
With MP84 Series Actuators — 50 sq. in. Effective Diaphragm Area
VG2831TM 2-1/2 54 65
/ 14 VG2831TM+843C00 60 / 19 VG2831TM+843D00 35 / 45 VG2831TM+843E00
VG2831UM 380 45
/ 10 VG2831UM+845C00 42 / 13 VG2831UM+845D00 24 / 31 VG2831UM+845E00
VG2831VM 4 157 25
/ 6 VG2831VM+845C00 23 / 8 VG2831VM+845D00 14 / 18 VG2831VM+845E00
With MP86 Series Actuators — 100 sq. in. Effective Diaphragm Area
VG2831UN 380 91
/ 21 VG2831UN+865C00 84 / 28 VG2831UN+865D00 49 / 63 VG2831UN+865E00
VG2831VN 4 157 51
/ 12 VG2831VN+865C00 47 / 16 VG2831VN+865D00 27 / 35 VG2831VN+865E00
VG2831WN 5 238 33
/ 7 VG2831WN+867C00 30 / 10 VG2831WN+867D00 18 / 23 VG2831WN+867E00
VG2831YN 6 347 23
/ 5 VG2831YN+867C00 21 / 7 VG2831YN+867D00 12 / 16 VG2831YN+867E00
Optional Positioner — Change the 00 at the end of the code number to either 01 or 02
Optional
Positioner
Mounting Bracket Type Control Input Output Capacity Ordering Code
V-9502-95 MP8000-6002 Pneumatic 2 to 12 psig Start
3 to 13 psig Span
1,000 scim – Dual Barbed Fitting
1,600 scim – 1/4 in. Barbed Fitting
01
EPP-1000-8 MP8000-6003 Electro-Pneumatic 0 to 10 VDC
4 to 20 mA
135 Ohm Slidewire
476 scim 02
Electric Damper Actuators
Flanged Globe or Ball
Valves and Actuators
Electric Damper Actuators
Flanged Globe or Ball
Valves and Actuators