Brochure

Table Of Contents
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2014 Johnson Controls, Inc.
www.johnsoncontrols.com
V–190
VG7000 Series Stainless Steel Trim Globe Valves with MP84 Series Pneumatic
Actuators (Continued)
Threaded Globe Valves and Actuators
Technical Specifications
VG7000 Series Stainless Steel Trim Globe Valves with MP84 Series Pneumatic Actuators
Service
1
1. Refer to the VDI 2035 Guideline for recommended proper water treatment.
Hot Water, Chilled Water, 50/50 Glycol Solutions, and Steam for HVAC Systems
Fluid Temperature Limits Water 35 to 338°F (2 to 170°C)
Steam 100 psig (690 kPa) Saturated Steam
Maximum Allowable
Pressure/Temperature
Water 400 psig (2,756 kPa) up to 150°F (66°C) Decreasing to 308 psig (2,122 kPa) at 338°F (170°C)
Steam 100 psig (690 kPa) Saturated Steam
Valve Body Pressure/Temperature Rating Meets Requirements of ANSI B16.15, Class 250
Maximum Recommended
Operating Pressure Drop
Water 30 psig (207 kPa) for 1-1/2 and 2 in. Valves
Steam 100 psig (690 kPa)
Flow Characteristics Two-Way Valves Equal Percentage
Three-Way Valves Linear Flow Characteristics
Rangeability
2
2. Rangeability is defined as the ratio of maximum controllable flow to minimum controllable flow.
> 100:1 According to EN60534-2-4
Leakage 0.05% of Maximum Flow per ANSI/FCI 70-2, Class 4
Actuator Ambient Operating Temperature Limits -20 to 150°F (-29 to 66°C)
Maximum Actuator Supply Pressure 25 psig (172 kPa) Maximum
Materials Body Cast Bronze
Bonnet Brass
Stem Stainless Steel
Plug Stainless Steel
Seat Stainless Steel
Packing Self-Adjusting Ethylene Propylene Rubber (EPR) Ring Pack U-Cups
Compliance Canada CRN: 0C1099.9087YTN
Threaded Globe Valves and
Actuators