VA9208-xxx-xx Series Electric Spring-Return Actuators (Continued)
Threaded Ball Valves and Actuators
VA9208-AGx-x Series On/Off and Floating Point Electric Spring-Return Actuators
Power Requirements -AGx Models AC 24 V (AC 19.2 V to 28.8 V) at 50/60 Hz: Class 2 (North America) or Safety Extra-Low Voltage
(SELV) (Europe), 7.9 VA Running, 5.5 VA Holding Position DC 24 V (DC 21.6 V to 28.8 V): Class 2
(North America) or SELV (Europe) 3.5 W Running, 1.9 W Holding Position
Minimum Transformer Size: 8 VA per Actuator
Input Signal/
Adjustments
-AGx Models AC 19.2 to 28.8 V at 50/60 Hz or DC 24 V +20%/-10% Class 2 (North America) or SELV (Europe)
Minimum Pulse Width: 500 ms
Control Input
Impedance
-AGx Models 3,000 Ohm Control Inputs
Auxiliary Switch Rating -xxC Models Two Single-Pole, Double-Throw (SPDT), Double-Insulated Switches with Gold over Silver Contacts:
AC 24 V, 50 VA Pilot Duty
AC 120 V, 5.8 A Resistive, 1/4 hp, 275 VA Pilot Duty
AC 240 V, 5.0 A Resistive, 1/4 hp, 275 VA Pilot Duty
Spring Return Direction is Selectable with Mounting Position of Actuator:
Actuator Face Labeled A is away from Valve: CCW Spring Return
Actuator Face Labeled B is away from Valve: CW Spring Return
Rated Torque Power On (Running) 70 lb·in (8 N·m) All Operating Temperatures
Power Off
(Spring Returning)
70 lb·in (8 N·m) All Operating Temperatures
Rotation Range Maximum Full Stroke: 95°
Rotation Time for 90
Degrees of Travel
Power On (Running) 150 Seconds for 0 to 70 lb·in (8 N·m) Load, at All Operating Conditions
Power Off
(Spring Returning)
17 to 25 Seconds for 0 to 70 lb·in (8 N·m) Load, at Room Temperature
22 Seconds Nominal at Full Rated Load
94 Seconds Maximum with 70 lb·in (8 N·m) Load, at -40°F (-40°C)
Life Cycles 60,000 Full Stroke Cycles with 70 lb·in (8 N·m) Load
1,500,000 Repositions with 70 lb·in (8 N·m) Load
Audible Noise Rating Power On (Running) < 35 dBA at 70 lb·in (8 N·m) Load, at a Distance of 39-13/32 in. (1 m)
Power On (Holding) < 20 dBA at a Distance of 39-13/32 in. (1 m)
Power Off
(Spring Returning)
< 52 dBA at 70 lb·in (8 N·m) Load, at a Distance of 39-13/32 in. (1 m)
Electrical Connections -AGx-3 Models 48 in. (1.2 m) UL 758 Type AWM Halogen-Free Cable with 18 AWG (0.85 mm
2
) Conductors and 1/4 in.
(6 mm) Ferrule Ends
-AGx-2 Models 120 in. (3.05 m) UL 444 Type CMP Plenum Rated Cable with 19 AWG (0.75 mm
2
) Conductors and
1/4 in. (6 mm) Ferrule Ends
Auxiliary Switches
(-xxC Models)
48 in. (1.2 m) UL 758 Type AWM Halogen-Free Cable with 18 AWG (0.85 mm
2
) Conductors and 1/4 in.
(6 mm) Ferrule Ends
Conduit Connections Integral Connectors for 3/8 in. (10 mm) Flexible Metal Conduit
Fluid Temperature
Limits
VG12x1 and VG18x1 Series 23 to 203°F (-5 to 95°C), Not Rated for Steam Service
VG12x5 and VG18x5 Series -22 to 212°F (-30 to 100°C), Not Rated for Steam Service
VG12x5 and VG18x5 Series
with M9000-561 Thermal
Barrier Installed
-22 to 284°F (-30 to 140°C) Water; 15 psig (103 kPa) at 250°F (121°C) Saturated Steam
Ambient Conditions Standard Operating -40 to 140°F (-40 to 60°C); 90% RH Maximum, Noncondensing
Storage -40 to 185°F (-40 to 85°C); 95% RH Maximum, Noncondensing
Enclosure Rating NEMA 2 (IP54) for All Mounting Directions
Compliance United States UL Listed, CCN XAPX, File E27734; to UL 60730-1A: 2003-08, Ed. 3.1, Automatic Electrical Controls
for Household and Similar Use; and UL 60730-2-14: 2002-02, Ed. 1, Part 2 Particular Requirements for
Electric Actuators
Canada UL Listed, CCN XAPX7, File E27734; to UL 60730-1:02-CAN/CSA: July 2002, 3rd Ed., Automatic
Electrical Controls for Household and Similar Use; and CSA C22.2 No. 24-93 Temperature Indicating
and Regulating Equipment
Europe CE Mark – Johnson Controls, Inc. declares that this product is in compliance with the essential
requirements and other relevant provisions of the EMC Directive 2004/108/EC and the Low Voltage
Directive 2006/95/EC.
Australia and New Zealand C-Tick Mark, Australia/NZ Emissions Compliant
Shipping Weight -AGA Models 3.5 lb (1.6 kg)
-AGC Models 3.9 lb (1.8 kg)