Brochure

Table Of Contents
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2014 Johnson Controls, Inc.
www.johnsoncontrols.com
V–153
VA9208-xxx-xx Series Electric Spring-Return Actuators (Continued)
Threaded Ball Valves and Actuators
Technical Specifications
VA9208-GGx-xx Series On/Off and Floating Electric Spring-Return Actuators
Power Requirements -GGx Models AC 24 V (AC 19.2 V to 28.8 V) at 50/60 Hz: Class 2 (North America) or Safety Extra-Low Voltage
(SELV) (Europe), 7.9 VA Running, 5.5 VA Holding Position DC 24 V (DC 21.6 V to 28.8 V): Class 2
(North America) or SELV (Europe)
3.5 W Running, 1.9 W Holding Position
Minimum Transformer Size: 8 VA per Actuator
Input Signal/
Adjustments
-GGx Models Factory Set at DC 0 to 10 V, CW Rotation with Signal Increase Selectable DC 0 (2) to 10 V or 0 (4) to
20 mA with Field Furnished 500 Ohm, 0.25 W Minimum Resistor; Switch Selectable Direct or Reverse
Action with Signal Increase
Control Input
Impedance
-GGx Models Voltage Input: 100,000 Ohms
Current Input: 500 Ohms with Field Furnished 500 Ohm Resistor
Feedback Signal -GGx Models DC 0 (2) to 10 V for Desired Rotation Range up to 95°
Corresponds to Rotation Limits, 0.5 mA at 10 V Maximum
Auxiliary Switch Rating -xxC Models Two Single-Pole, Double-Throw (SPDT), Double-Insulated Switches with Gold over Silver Contacts:
AC 24 V, 50 VA Pilot Duty
AC 120 V, 5.8 A Resistive, 1/4 hp, 275 VA Pilot Duty
AC 240 V, 5.0 A Resistive, 1/4 hp, 275 VA Pilot Duty
Spring Return Direction is Selectable with Mounting Position of Actuator:
Actuator Face Labeled A is away from Valve: CCW Spring Return
Actuator Face Labeled B is away from Valve: CW Spring Return
Rated Torque Power On (Running) 70 lb·in (8 N·m) All Operating Temperatures
Power Off
(Spring Returning)
70 lb·in (8 N·m) All Operating Temperatures
Rotation Range Maximum Full Stroke: 9
Adjustable Stop: 35° to 95° Maximum Position
Rotation Time for 90
Degrees of Travel
Power On (Running) 150 Seconds Constant for 0 to 70 lb·in (8 N·m) Load, at All Operating Conditions
90 Seconds for 0 to 70 lb·in (8 N·m) in Calibration Mode or Override Mode
Power Off
(Spring Returning)
17 to 25 Seconds for 0 to 70 lb·in (8 N·m) Load, at Room Temperature
22 Seconds Nominal at Full Rated Load
94 Seconds Maximum with 70 lb·in (8 N·m) Load, at -40°F (-40°C)
Life Cycles 60,000 Full Stroke Cycles with 70 lb·in (8 N·m) Load
1,500,000 Repositions with 70 lb·in (8 N·m) Load
Audible Noise Rating Power On (Running) < 35 dBA at 70 lb·in (8 N·m) Load, at a Distance of 39-13/32 in. (1 m)
Power On (Holding) < 20 dBA at a Distance of 39-13/32 in. (1 m)
Power Off
(Spring Returning)
< 52 dBA at 70 lb·in (8 N·m) Load, at a Distance of 39-13/32 in. (1 m)
Electrical Connections -GGx-3 Models 48 in. (1.2 m) UL 758 Type AWM Halogen-Free Cable with 18 AWG (0.85 mm
2
) Conductors and 1/4 in.
(6 mm) Ferrule Ends
-GGx-2 Models 120 in. (3.05 m) UL 444 Type CMP Plenum Rated Cable with 19 AWG (0.75 mm
2
) Conductors and
1/4 in. (6 mm) Ferrule Ends
Auxiliary Switches
(-xxC Models)
48 in. (1.2 m) UL 758 Type AWM Halogen-Free Cable with 18 AWG (0.85 mm
2
) Conductors and 1/4 in.
(6 mm) Ferrule Ends
Conduit Connections Integral Connectors for 3/8 in. (10 mm) Flexible Metal Conduit
Fluid Temperature
Limits
VG12x1 and VG18x1 Series 23 to 203°F (-5 to 95°C), Not Rated for Steam Service
VG12x5 and VG18x5 Series -22 to 212°F (-30 to 100°C), Not Rated for Steam Service
VG12x5 and VG18x5 Series
with M9000-561 Thermal
Barrier Installed
-22 to 284°F (-30 to 140°C) water; 15 psig (103 kPa) at 250°F (121°C) Saturated Steam
Ambient Conditions Standard Operating -40 to 140°F (-40 to 60°C); 90% RH Maximum, Noncondensing
Storage -40 to 185°F (-40 to 85°C); 95% RH Maximum, Noncondensing
Enclosure Rating NEMA 2 (IP54) for All Mounting Directions
Compliance United States UL Listed, CCN XAPX, File E27734; to UL 60730-1A: 2003-08, Ed. 3.1, Automatic Electrical Controls
for Household and Similar Use; and UL 60730-2-14: 2002-02, Ed. 1, Part 2 Particular Requirements for
Electric Actuators
Canada UL Listed, CCN XAPX7, File E27734; to UL 60730-1:02-CAN/CSA: July 2002, 3rd Ed., Automatic
Electrical Controls for Household and Similar Use; and CSA C22.2 No. 24-93 Temperature Indicating
and Regulating Equipment
Europe CE Mark – Johnson Controls, Inc. declares that this product is in compliance with the essential
requirements and other relevant provisions of the EMC Directive 2004/108/EC and the Low Voltage
Directive 2006/95/EC.
Australia and New Zealand C-Tick Mark, Australia/NZ Emissions Compliant
Shipping Weight -GGA Models 3.5 lb (1.6 kg)
-GGC Models 3.9 lb (1.8 kg)
Threaded Ball Valves and
Actuators
Threaded Ball Valves and
Actuators
Threaded Ball Valves and
Actuators
Threaded Ball Valves and
Actuators