Brochure

Table Of Contents
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2014 Johnson Controls, Inc.
www.johnsoncontrols.com
V–152
VA9208-xxx-xx Series Electric Spring-Return Actuators (Continued)
Threaded Ball Valves and Actuators
Selection Chart
Code Number Rotation Time
(Seconds) for 90°
Power
Requirement
Power Consumption Input Signal Position
Feedback
Auxiliary
Switches
Electrical
Connection
Power On (Running)
Power Off (Spring Return)
24 VAC +/- 25% VDC +20%/-10%
24 VAC +/- 20% VDC +20%/-10%
120 VAC +/- 10%
230 VAC +/- 10%
VA Rating, Transformer Sizing
VA: Running (Holding)
Amperage: Running (Holding)
On/Off
Floating Point
0(2) to 10 VDC
0(4) to 20 mA (with 500 Ohm Resistor)
0(2) to 10 VDC
2 SPDT, 5.0 A (2.9 A Inductive) at 240 V
48 in. (1.2 m) 18 AWG Appliance Cable
120 in. (3.05 m) 19 AWG Plenum Cable
Integral 3/8 in. FMC Connectors
VA9208-AGA-2
150
17 to 25
1
1. 22 seconds nominal at room temperature and rated load, 94 seconds maximum at rated load and -40°F (-40°C).
87.9 (5.5) ■■
VA9208-AGA-3
150
17 to 25
1
87.9 (5.5) ■■
VA9208-AGC-3
150
17 to 25
1
87.9 (5.5) ■■
VA9208-BGA-3
55 to 71
13 to 26
2
2. 21 seconds nominal at room temperature and rated load, 39 seconds maximum at rated load and -4°F (-20°C), 108 seconds maximum at 53 lb·in (6 N·m) and
-40°F (-40°C).
76.1 (1.2) ■■
VA9208-BGC-3
55 to 71
13 to 26
2
76.1 (1.2) ■■
VA9208-BAA-3
55 to 71
13 to 26
2
0.05 (0.03) ■■
VA9208-BAC-3
55 to 71
13 to 26
2
0.05 (0.03) ■■
VA9208-BDA-3
55 to 71
13 to 26
2
0.04 (0.03) ■■
VA9208-BDC-3
55 to 71
13 to 26
2
0.04 (0.03) ■■
VA9208-GGA-2
150
17 to 25
1
87.9 (5.5) ■■
VA9208-GGA-3
150
17 to 25
1
87.9 (5.5) ■■
VA9208-GGC-3
150
17 to 25
1
87.9 (5.5) ■■
Threaded Ball Valves and
Actuators
Threaded Ball Valves and
Actuators