Brochure

Table Of Contents
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2014 Johnson Controls, Inc.
www.johnsoncontrols.com
V–141
VG1000 Series Sweat End Connection Stainless Steel Trim Ball Valves (Continued)
Threaded Ball Valves and Actuators
Accessories and Repair Parts
Technical Specifications
Three-Way Spring Return Clockwise, Port B (Bypass) Open
VG1875AD 1/2 1.2
/ 0.7
1
200 VG1875AD+943AGA VG1875AD+943GGA VG1875AD+943BGA VG1875AD+943BUA
VG1875AE 1.9
/ 1.2
1
VG1875AE+943AGA VG1875AE+943GGA VG1875AE+943BGA VG1875AE+943BUA
VG1875AF 2.9
/ 1.9
1
VG1875AF+943AGA VG1875AF+943GGA VG1875AF+943BGA VG1875AF+943BUA
VG1875AG 4.7
/ 2.9
1
VG1875AG+943AGA VG1875AG+943GGA VG1875AG+943BGA VG1875AG+943BUA
VG1875AL 7.4
/ 4.7
1
VG1875AL+943AGA VG1875AL+943GGA VG1875AL+943BGA VG1875AL+943BUA
VG1875AN 11.7
/ 5.8 VG1875AN+943AGA VG1875AN+943GGA VG1875AN+943BGA VG1875AN+943BUA
VG1875BG 3/4 4.7
/ 2.9
1
200 VG1875BG+943AGA VG1875BG+943GGA VG1875BG+943BGA VG1875BG+943BUA
VG1875BL 7.4
/ 4.7
1
VG1875BL+943AGA VG1875BL+943GGA VG1875BL+943BGA VG1875BL+943BUA
VG1875BN 11.7
/ 5.8 VG1875BN+943AGA VG1875BN+943GGA VG1875BN+943BGA VG1875BN+943BUA
VG1875CL 17.4
/ 4.7
1
200 VG1875CL+943AGA VG1875CL+943GGA VG1875CL+943BGA VG1875CL+943BUA
VG1875CN 11.7
/ 7.4
1
VG1875CN+943AGA VG1875CN+943GGA VG1875CN+943BGA VG1875CN+943BUA
VG1875CP 18.7
/ 9.4 VG1875CP+943AGA VG1875CP+943GGA VG1875CP+943BGA VG1875CP+943BUA
1. Valve has a characterizing disk.
Linkage Replacement Description
M9000-551 Ball Valve Linkage Kit with Handle for M9104 Series Actuators
M9000-560 Ball Valve Linkage Kit for M9203 Series Actuators
M9000-561 Thermal Barrier for VA9104 and VA9203 Series Actuators
VG1000 Series Sweat End Connection Stainless Steel Trim Ball Valves
Service
1
1. Proper water treatment is recommended; refer to the VDI 2035 Guideline.
Hot Water, Chilled Water, and 50/50 Glycol Solutions for HVAC Systems
Fluid Temperature Limits, without M9000-561 Thermal Barrier -22 to 212F (-30 to 100C)
Fluid Temperature Limits, with M9000-561 Thermal Barrier -22 to 284°F (-30 to 100°C)
Valve Body Pressure Rating 300 psig, PN40
Maximum Closeoff Pressure 200 psid (1,378 kPa)
Maximum Recommended Operating Pressure Drop 50 psi (340 kPa)
Flow Characteristics Two-Way Equal Percentage
Three-Way Equal Percentage Flow Characteristics on the In-Line Port A (Coil) and Linear
Flow Characteristics of the Angle Port B (Bypass)
Rangeability
2
2. Rangeability is defined as the ratio of maximum controllable flow to minimum controllable flow.
Greater than 500:1
Minimum Ambient Operating
Temperature
With VA9203 Series Spring-Return
Actuators
-22°F (-30°C)
With M9104 Series Non-Spring-Return
Actuators
-4°F (-20°C)
Maximum Ambient Operating
Temperature (Limited by the
Actuator)
With VA9203 Series Spring-Return
Actuators
140°F (60°C)
With VA9104 Series
Non-Spring-Return Actuators
140°F (60°C)
Leakage 0.01% of Maximum Flow per ANSI/FCI 70-2, Class 4
End Connections Sweat
Note: Use a Low Melting Point Solder.
Materials Body Forged Brass
Ball 300 Series Stainless Steel
Blowout-proof Stem 300 Series Stainless Steel
Seats Graphite-Reinforced PTFE with Ethylene Propylene Diene Monomer
(EPDM)
O-Ring Backing
Stem Seals EPDM Double O-Rings
Characterizing Disk Amodel® AS-1145HS Polyphtalamide Resin
VG1000 Sweat End Connection Valves, Stainless Steel Trim, Spring-Return Actuators (Part 2 of 2)
Valve Code
Number
Size,
in.
Cv
(Control
Port) / Cv
(Bypass
Port)
Closeoff
psig
AC 24 V AC 85-264 V
Floating DC 0 to 10 V
Proportional
On/Off On/Off
VA9203-AGA-2Z VA9203-GGA-2Z VA9203-BGA-2 VA9203-BUA-2
Threaded Ball Valves and
Actuators
Threaded Ball Valves and
Actuators
Threaded Ball Valves and
Actuators
Threaded Ball Valves and
Actuators