V–138
VG1000 Series Sweat End Connection Plated Brass Trim Ball Valves (Continued)
Threaded Ball Valves and Actuators
Accessories and Repair Parts
Technical Specifications
Three-Way Spring Return Clockwise, Port B (Bypass) Open
VG1871AD 1/2 1.2
1
200 VG1871AD+943AGA VG1871AD+943GGA VG1871AD+943BGA VG1871AD+943BUA
VG1871AE 1.9
1
VG1871AE+943AGA VG1871AE+943GGA VG1871AE+943BGA VG1871AE+943BUA
VG1871AF 2.9
1
VG1871AF+943AGA VG1871AF+943GGA VG1871AF+943BGA VG1871AF+943BUA
VG1871AG 4.7
1
VG1871AG+943AGA VG1871AG+943GGA VG1871AG+943BGA VG1871AG+943BUA
VG1871AL 7.4
1
VG1871AL+943AGA VG1871AL+943GGA VG1871AL+943BGA VG1871AL+943BUA
VG1871AN 11.7 VG1871AN+943AGA VG1871AN+943GGA VG1871AN+943BGA VG1871AN+943BUA
VG1871BG 3/4 4.7
1
200 VG1871BG+943AGA VG1871BG+943GGA VG1871BG+943BGA VG1871BG+943BUA
VG1871BL 7.4
1
VG1871BL+943AGA VG1871BL+943GGA VG1871BL+943BGA VG1871BL+943BUA
VG1871BN 11.7 VG1871BN+943AGA VG1871BN+943GGA VG1871BN+943BGA VG1871BN+943BUA
VG1871CL 17.4
1
200 VG1871CL+943AGA VG1871CL+943GGA VG1871CL+943BGA VG1871CL+943BUA
VG1871CN 11.7
1
VG1871CN+943AGA VG1871CN+943GGA VG1871CN+943BGA VG1871CN+943BUA
VG1871CP 18.7 VG1871CP+943AGA VG1871CP+943GGA VG1871CP+943BGA VG1871CP+943BUA
1. Valve has a characterizing disk.
Linkage Replacement Description
M9000-551 Ball Valve Linkage Kit with Handle for M9104 Series Actuators
M9000-560 Ball Valve Linkage Kit for M9203 Series Actuators
VG1000 Series Sweat End Connection Plated Brass Trim Ball Valves
Service
1
1. Proper water treatment is recommended; refer to the VDI 2035 Guideline.
Hot Water, Chilled Water, and 50/50 Glycol Solutions for HVAC Systems
Fluid Temperature Limits 23 to 203°F (-5 to 95°C)
Valve Body Pressure Rating 300 psig, PN40
Maximum Closeoff Pressure 200 psid (1,378 kPa)
Maximum Recommended Operating Pressure
Drop
50 psid (340 kPa)
Flow Characteristics Two-Way Equal Percentage
Three-Way Equal Percentage Flow Characteristics on the In-Line Port A (Coil) and Linear Flow Characteristics of the
Angle Port B (Bypass)
Rangeability
2
2. Rangeability is defined as the ratio of maximum controllable flow to minimum controllable flow.
Greater than 500:1
Minimum Ambient
Operating
Temperature
With VA9203 Series
Spring-Return Actuators
-22°F (-30°C)
With VA9104 Series
Non-Spring-Return
Actuators
-4°F (-20°C)
Maximum Ambient
Operating
Temperature
With VA9203 Series
Spring-Return Actuators
122°F (50°C)
With VA9104 Series
Non-Spring-Return
Actuators
140°F (60°C)
Leakage 0.01% of Maximum Flow per ANSI/FCI 70-2, Class 4
End Connections Sweat
Note: Use a Low Melting Point Solder.
Materials Body Forged Brass
Ball Chrome Plated Brass
Blowout Proof Stem Nickel Plated Brass
Seats Graphite-Reinforced PTFE with Ethylene Propylene Diene Monomer (EPDM) O-Ring Backing
Stem Seals EPDM Double O-Rings
Characterizing Disk Amodel® AS-1145HS Polyphtalamide Resin
VG1000 Sweat End Connection Valves, Brass Trim, Spring-Return Actuators (Part 2 of 2)
Valve Code
Number
Size,
in.
Cv
(Control
Port) / Cv
(Bypass
Port)
Closeoff
psig
AC 24 V AC 120 V
Floating DC 0 to 10 V
Proportional
On/Off On/Off
VA9203-AGA-2Z VA9203-GGA-2Z VA9203-BGA-2 VA9203-BUA-2
Threaded Ball Valves and
Actuators
Threaded Ball Valves and
Actuators