Brochure

Table Of Contents
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2014 Johnson Controls, Inc.
www.johnsoncontrols.com
V–135
VG1000 Series Forged Brass Ball Valves for Assembly in the Field (Continued)
Threaded Ball Valves and Actuators
Technical Specifications
VG1000 Series Forged Brass Ball Valves for Assembly in the Field
Service
1
1. Refer to the VDI 2035 Guideline for recommended proper water treatment.
Hot Water, Chilled Water, 50/50 Glycol Solutions, and 15 psig (103 kPa) Saturated Steam
2
for
HVAC Systems
2. In steam applications, install the valve with the stem horizontal to the piping and wrap the valve and piping with insulation.
Fluid Temperature Limits Water VG12x1 and VG18x1 Series: 23 to 203F (-5 to 95C)
VG12x5 and VG18x5 Series: -22 to 284F (-30 to 140C)
Steam
2
VG12x1 and VG18x1 Series: Not Rated for Steam Service
VG12x5 and VG18x5 Series: 15 psig (103 kPa) at 250°F (121°C)
Maximum Actuator Fluid
Temperature Limits
212°F (100°C) VA9104, VA9203, VA9208, M9104 with M9000-550 Linkage
284°F (140°C) M9106, M9109, VA9104, VA9203, or VA9208 with M9000-561 Thermal Barrier
Valve Body Pressure Rating Water VG1241, VG1245, VG1841, and VG1845 Series: 580 psig (4,000 kPa) (PN40), 464 psig
(3,196 kPa) at 284°F (140°C) (PN40)
VG1275 and VG1875 Series: 300 psig (2,067 kPa)
VG1295 and VG1895 Series: 300 psig (2,067 kPa)
Steam
2
15 psig (103 kPa) Saturated Steam
Maximum Closeoff Pressure VG12x1 and
VG12x5 Series:
200 psid (1,378 kPa)
Maximum Recommended Operating Pressure Drop 50 psid (340 kPa)
Flow Characteristics Two-Way Equal Percentage
Three-Way Equal Percentage Flow Characteristics of In-Line Port (Coil) and Linear Flow Characteristics of
Angle Port (Bypass)
Rangeability
3
3. Rangeability is defined as the ratio of maximum controllable flow to minimum controllable flow.
Greater than 500:1
Minimum Ambient Operating
Temperature
-4°F (-20°C) M9106, M9104, M9109, and VA9104 Series Non-Spring-Return Actuators
-22°F (-30°C) VA9203 Series Spring-Return Actuators
-40°F (-40°C) VA9208 Series Spring-Return Actuators
Maximum Ambient
Operating Temperature
2
(Limited by
the Actuator and Linkage)
Direct Mount 140°F (60°C): VA9104 Series Non-Spring-Return Actuators
Direct Mount or with
M9000-561 Thermal
Barrier
140°F (60°C): VA9203 and VA9208 Series Spring-Return Actuators
M9000-551 Linkage 140°F (60°C): M9104 Series Non-Spring-Return Actuators
M9000-520 Linkage 125°F (52°C): M9106 and M9109 Series Non-Spring-Return Actuators
M9000-51x Series
Linkage
125°F (52°C): M9106 Series Non-Spring-Return Actuators
122°F (50°C): M9100 Series Non-Spring-Return Actuators
Leakage 0.01% of Maximum Flow per ANSI/FCI 70-2, Class 4
1% of Maximum Flow for Three-Way Bypass Port
End Connections NPT: 1/2 through 2 in.
Sweat: 1/2 through 1 in. (DN15 through DN25)
Press (ProPress® Compatible): 1/2 through 1 in. (DN15 through DN25)
Materials Body Forged Brass
Ball VG12x1 and VG18x1 Series: Chrome Plated Brass
VG12x5 and VG18x5 Series: 300 Series Stainless Steel
Blowout-Proof Stem VG12x1 and VG18x1 Series: Nickel Plated Brass
VG12x5 and VG18x5 Series: 300 Series Stainless Steel
Seats Graphite-Reinforced PTFE with EPDM O-Ring Backing
Stem Seals EPDM Double O-Rings
Characterizing Disk AMODEL
® AS-1145HS Polyphthalamide Resin
Threaded Ball Valves and
Actuators
Threaded Ball Valves and
Actuators
Threaded Ball Valves and
Actuators
Threaded Ball Valves and
Actuators