The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2014 Johnson Controls, Inc.
www.johnsoncontrols.com
V–115
VG1000 Series Three-Way, Stainless Steel Trim, NPT End Connections Ball Valves with
Non-Spring-Return Electric Actuators (Continued)
Threaded Ball Valves and Actuators
Technical Specifications
VG1000 Series Three-Way, Stainless Steel Trim, NPT End Connections Ball Valves with Non-Spring-Return Electric Actuators
Service
1
1. Proper water treatment is recommended; refer to the VDI 2035 Guideline.
Hot Water, Chilled Water, 50/50 Glycol Solutions, and 15 psig (103 kPa) Saturated Steam for
HVAC Systems
Fluid Temperature Limits Water -22 to 284F (-30 to 140C)
Steam 15 psig (103 kPa) at 250°F (121°C)
Maximum Actuator Fluid
Temperature Limits
212°F (100°C) VA9104 Series
M9104 with M9000-550 Linkage
284°F (140°C) VA9104 Series Non-Spring-Return Actuators
M9106 or M9109 Series Non-Spring-Return Actuators with M9000-520 Linkage
Valve Body Pressure/Temperature
Rating
Water 580 psig (4,000 kPa) (PN40)
Steam 15 psig (103 kPa) Saturated Steam
Maximum Closeoff Pressure 200 psid (1,378 kPa)
Maximum Recommended Operating Pressure Drop 50 psid (340 kPa)
Flow Characteristics Three-Way Equal Percentage Flow Characteristics of In-Line Port A (Coil) and Linear Flow Characteristics of
Angle Port B (Bypass)
Rangeability
2
2. Rangeability is defined as the ratio of maximum controllable flow to minimum controllable flow.
Greater than 500:1
Minimum Ambient Operating Temperature -4°F (-20°C)
Maximum Ambient
Operating Temperature
3
(Limited by
the Actuator and Linkage)
3. In steam applications, install the valve with the stem horizontal to the piping and wrap the valve and piping with insulation.
140°F (60°C) VA9104 Series Non-Spring-Return Actuators
M9104 Series Non-Spring-Return Actuators with M9000-550 Linkage
125°F (52°C) M9106 or M9109 Series Non-Spring-Return Actuators with M9000-520 Linkage
Leakage 0.01% of Maximum Flow per ANSI/FCI 70-2, Class 4
End Connections National Pipe Thread (NPT)
Materials Body Forged Brass
Ball 300 Series Stainless Steel
Blowout-Proof Stem 300 Series Stainless Steel
Seats Graphite-Reinforced Polytetrafluoroethylene (PTFE) with Ethylene Propylene Diene Monomer
(EPDM) O-Ring Backing
Stem Seals EPDM Double O-Rings
Characterizing Disk Amodel
® AS-1145HS Polyphthalamide Resin
Threaded Ball Valves and
Actuators
Threaded Ball Valves and
Actuators
Threaded Ball Valves and
Actuators
Threaded Ball Valves and
Actuators