Actuator Install Instructions
Table Of Contents
VA9208-Bxx-x Series On/Off Electric Spring Return Valve Actuators Installation Instructions6
3. Remove the linkage from Side B (Figure 11).
4. Insert the drive shaft into Side A (Figure 12).
5. Install linkage base on Side A using the two 
#10-14 x 2.75 in. long screws (Figure 13). The 
recommended torque is 20 to 24 lb·in. 
(2.3 to 2.7 N·m). 
6. Insert fixed pointer and M4x0.7x83 mm long screw 
into the Side B actuator hub. Direct the arrow on 
the pointer to 0% (Figure 14). 
Figure 11: Removing the Linkage
Figure 12: Inserting the Drive Shaft
Figure 13: Installing the Linkage
F
I
G
:
l
n
k
g
A
Figure 14: Installing the Fixed Pointer