Valve Install Instructions
Table Of Contents
VG1000 Series Forged Brass Ball Valves Installation Instructions2
For more detailed installation information about the 
specific equipment used, refer to the appropriate 
document from the following list:
• VA9104-xGA-2S Series Electric Non-Spring Return 
Valve Actuators Installation Instructions 
(Part No. 14-1336-15)
• VA9104-xGA-3S Series Electric Non-Spring Return 
Valve Actuators Installation Instructions 
(Part No. 14-1336-23)
• M9102-AGA-2S and M9104-xGA-2S Series 
Electric Non-Spring Return Actuators Installation 
Instructions (Part No. 34-636-1220)
• M9102-AGA-3S and M9104-xGA-3S Series 
Electric Non-Spring Return Actuators Installation 
Instructions (Part No. 34-636-1433)
• M9106-xGx-2 Series Electric Non-Spring Return 
Actuators Installation Instructions 
(Part No. 34-636-1085)
• M9109 Series Electric Non-spring Return 
Actuators Installation Instructions 
(Part No. 34-636-1190)
• VA9203-AGx-2Z Series On/Off and Floating Point 
Electric Spring Return Valve Actuators Installation 
Instructions (Part No. 14-1380-8)
• VA9203-Bxx-2 Series On/Off Spring Return Valve 
Actuators Installation Instructions 
(Part No. 14-1380-16)
• VA9203-GGx-2Z Series Proportional Spring Return 
Valve Actuators Installation Instructions 
(Part No. 14-1380-24)
• VA9208-AGx-x Series On/Off and Floating Point 
Electric Spring Return Valve Actuators Installation 
Instructions (Part No. 14-1379-5)
• VA9208-Bxx-x Series On/Off Spring Return Valve 
Actuators Installation Instructions 
(Part No. 14-1379-13)
• VA9208-GGx-x Series Proportional Spring Return 
Valve Actuators Installation Instructions
(Part No. 14-1379-21)
• M9108, M9116, M9124, and M9132 Series Electric 
Non-Spring Return Actuators Installation 
Instructions (Part No. 34-636-399)
• M9210-AGx-3 Floating Electric Spring Return 
Actuators Installation Instructions 
(Part No. 34-636-1654)
• M9210-Bxx-3 On/Off Electric Spring Return 
Actuators Installation Instructions 
(Part No. 34-636-1638)
• M9210-GGx-3 Proportional Electric Spring Return 
Actuators Installation Instructions 
(Part No. 34-636-1662)
• M2000-560 Ball Valve Linkage Kit and M9000-561 
Thermal Barrier Installation Instructions 
(Part No. 34-636-2227)
• M9000-330 and M9000-340 Series Weather Shield 
Enclosures Installation Instructions 
(Part No. 14-1330-26)
• M9000-341 Series Weather Shield Enclosures 
Installation Instructions (Part No. 34-636-2235)
• M9000-51x Series Valve Linkage Kits Installation 
Instructions (Part No. 14-1201-13)
• M9000-520 Ball Valve Linkage Kit Installation 
Instructions (Part No. 14-1297-5)
• M9000-551 Ball Valve Linkage Kit Installation 
Instructions (Part No. 34-636-1816)
Note: To avoid excessive wear or drive time on the 
motor for VA9104, M9104, M9106, and M9109 AGx 
models, use a controller and/or software that provides 
a time-out function to remove the signal at the end of 
rotation (stall). The IGx and GGx models have an auto 
shutoff to avoid excessive wear or drive time on the 
motor.
On models with the flow-characterizing disk, the disk is 
located in Port A. Port A must be the inlet. On 
three-way models, use Port A as the coil inlet and 
Port B as the bypass inlet.
IMPORTANT: Take care to prevent foreign material 
such as weld slag, thread burrs, metal chips, and 
scale from entering the piping system. This debris 
can damage or severely impede the operation of the 
valve by embedding itself in the seats, scoring the 
valve, and ultimately resulting in seat leakage. If the 
debris becomes embedded in the seats, subsequent 
flushing and filtering of the piping system with the 
valve installed does not remedy the problem.