To mount the actuator:
1. Turn valve stem to position below. 
2. Mount optional M9000-561 Thermal Barrier to the 
valve if fluid temperature exceeds 212°F (100°C). 
See the Mounting the Thermal Barrier
 section for 
more information.
3. Place the handle the top of the drive shaft 
(Figure 5). The handle is keyed on and can only be 
mounted in one orientation.
4. Check that the actuator coupler and handle are in 
the full counterclockwise position as viewed from 
the top of the actuator. If not, press the actuator 
gear release and rotate the handle until the 
actuator coupler is fully counterclockwise.
5. Install the valve actuator over the ball valve 
mounting flange. Depending on the installation, 
position the assembly in any one of four 90° 
increments on the valve.
Note: For proper operation, the actuator must 
drive the valve counterclockwise to open Port A 
when viewed from above the valve
6. To secure the actuator to the valve, use a 1/4 in. 
(6 mm) flat blade screwdriver. Recommended 
torque is 8to12lbin (0.9 to 1.4 Nm). 
Figure 4: Positioning the Valve Stem
F
I
G
:
V
G
1
0
0
0
3 Way2 Way
Figure 5: Installing the Handle
F
I
G
:
h
n
d
l
IMPORTANT: Do not overtighten the manual 
handle mounting screw. Overtightening may strip 
the threads resulting in damage to the valve stem 
threads.
Figure 6: Coupling the Actuator to the Valve
F
I
G
:
C
U
P
L
A
C
T