VA9104-xGA-3S Series Electric Non-Spring Return Valve Actuators Installation Instructions6
Wiring  
VA9104-AGA-3S and VA9104-IGA-3S
The VA9104-AGA and VA9104-IGA Series Electric 
Non-Spring Return Valve Actuators require an AC 24 V 
input signal and work with a variety of controllers. 
These electric actuators include M3 Screw terminals; 
see Figure 10 and Figure 11 to wire the applicable 
VA9104 Series model. 
Note: For all VA9104-AGA Series Actuators, use a 
controller and/or software that provides a timeout 
function at the end of rotation (stall) to avoid excessive 
wear or drive time on the actuator motor. The -GGA 
and -IGA models have an auto shutoff feature to 
prevent excessive wear or drive time on the motor.
VA9104-GGA-3S
The VA9104-GGA Series Electric Non-Spring Return 
valve actuators require AC 24 V power and a 
DC 0(2) to 10 V or 0(4) to 20 mA controller input signal. 
These electric actuators include M3 screw terminals; 
see Figure 12 for proper wiring. 
!
WARNING: Risk of Electric Shock.
Disconnect or isolate all power supplies 
before making electrical connections. 
More than one disconnect or isolation 
may be required to completely 
de-energize equipment. Contact with 
components carrying hazardous voltage 
can cause electric shock and may result 
in severe personal injury or death.
!
CAUTION: Risk of Property Damage.
Do not apply power to the system before 
checking all wiring connections. Short 
circuited or improperly connected wires 
may result in permanent damage to the 
equipment.
!
CAUTION: Risk of Property Damage.
Insulate and secure each unused wire 
lead before applying power to the 
actuator. Failure to insulate and secure 
each unused wire lead may result in 
property damage.
IMPORTANT: Make all wiring connections in 
accordance with the National Electrical Code and 
local regulations. Use proper Electrostatic Discharge 
(ESD) precautions during installation and servicing 
to avoid damaging the electronic circuits of the 
actuator.
~~
AC 24 V 50/60 Hz
321
~
Figure 10: VA9104-AGA-3S 
Control Wiring Diagram
~~
AC 24 V 50/60 Hz
3
~
12
Figure 11: VA104-IGA-3 