VA9203-Bxx-2 Series On/Off Electric Spring Return Valve Actuators Installation Instructions4
Mounting
Mounting the Actuator to Spring Return Port A 
(Coil) Open
To mount the actuator to spring return Port A (coil) 
open:
1. Turn the valve stem to the position outlined in 
Figure 4. 
2. Mount optional M9000-561 Thermal Barrier to the 
valve if fluid temperature exceeds 212°F (100°C). 
See the Mounting the Thermal Barrier
 section for 
more information.
Note: Proceed to Step 7 if the ball valve linkage is on 
actuator Side B.
3. Remove the linkage from Side A (Figure 5).
4. Insert the drive shaft into Side B (Figure 6). The 
drive shaft is keyed for one-way assembly. With 
gentle pressure applied, rotate the drive shaft until 
the key aligns and the drive shaft falls into place. 
5. Install linkage base on Side B using the two 
#8-32 x 0.625 in. long screws (Figure 7). The 
recommended torque is 29 to 33 lb·in. 
(3.3 to 3.7 N·m). 
Figure 4: Positioning the Valve Stem
F
I
G
:
V
G
1
0
0
0
3 Way2 Way
Figure 5: Removing the Linkage
F
I
G
:
R
M
V
_
L
N
K
Figure 6: Inserting the Drive Shaft
F
I
G
:
D
R
V
_
S
H
F
T
Figure 7: Installing the Linkage
F
I
G
:
I
N
S
T
_
L
N
K