Actuator Install Instructions
Table Of Contents
VA9203-Bxx-2 Series On/Off Electric Spring Return Valve Actuators Installation Instructions  9
Using Conduit
All VA9203 Series Actuators accept 1/2 in. threaded 
electrician’s fittings (Figure 21).
1. Feed the actuator cables through the field-supplied 
electrician’s fitting and conduit.
2. Thread the electrician’s fitting into the actuator and 
secure the conduit to the fitting in accordance with 
local building code requirements.
Setup and Adjustments
Auxiliary Switch (VA9203-xxB-xx Models)
The VA9203-xxB-xx models include one integral 
auxiliary switch with a switch adjuster accessible on 
either face of the actuator (Figure 22). The factory 
setting for Auxiliary Switch is 10% closing (relative to 
the 0 to 100% rotation range as printed on the product 
label). See the Technical Specifications
 section for the 
auxiliary switch ratings. 
The switch point is continuously adjustable throughout 
the actuators’s rotation range. For the most accurate 
switch positioning, see Figure 22 and use the method 
in the following example. To change the switch point of 
auxiliary switch, proceed as follows:
1. Position the actuator in the full spring return 
position.
Note: The switch is factory set to trip when the 
actuator reaches the 10% position.
2. Rotate the switch adjuster until it points to the 
desired switch point.
3. Connect the auxiliary switch to a power source or 
an ohmmeter and apply power to the actuator. The 
actuator moves to the fully open position and holds 
while power is applied.
4. Observe the switch point. If required, repeat Step 1 
through Step 3.
Figure 21: Adding Flexible Metal Conduit
!
WARNING: Risk of Electric Shock and 
Property Damage.
Insulate and secure each unused wire 
lead before applying power to the 
actuator. Failure to insulate and secure 
each unused wire lead may result in 
property damage, electric shock, and 
severe personal injury or death.
Figure 22: Switch Trip Point Settings