6. Insert fixed pointer and M4x0.7x83 mm long screw 
into the Side A actuator hub (Figure 8). Direct the 
arrow on the pointer to 100%. 
7. Install the actuator on the ball valve (Figure 9). 
Tighten the actuator mounting screw to a torque of 
10 to 12 lb·in. (1.1 to 1.4 N·m) and snap the large 
adjustable pointer into place. 
Mounting the Actuator to Spring Return Port A 
(Coil) Closed
To mount the actuator to spring return Port A (coil) 
closed:
1. Turn the valve stem to the position outlined in 
Figure 10. 
2. Mount optional M9000-561 Thermal Barrier to the 
valve if fluid temperature exceeds 212°F (100°C). 
See the Mounting the Thermal Barrier
 section for 
more information.
Note: Proceed to Step 7 if the ball valve linkage is on 
actuator Side A.
3. Remove the linkage from Side B (Figure 13).
Figure 8: Installing the Fixed 
Pointer
F
I
G
:
F
X
P
T
Figure 9: Mount the Actuator
F
I
G
:
M
N
T
_
A
C
T
Figure 10: Positioning the Valve Stem
F
I
G
:
V
G
1
0
0
0
s
d
B
2 Way
3 Way
Figure 11: Removing the Linkage
F
I
G
:
R
M
V
_
L
N
K
_
B