Product Overview
Table Of Contents
8 VA-4233 Series Electric Valve Actuators Product Bulletin
Technical Data (Cont.)
Operating 32 to 122°F (0 to 50°C)Ambient
Temperature Limits
Storage -85 to 185°F (-65 to 85°C)
Maximum Ambient
Humidity Limits
90% RH Non-Condensing at 70°F (21°C) Ambient Temperature
and 40°F (4°C) Fluid Temperature
Fluid Temperature Limits
(Actuator and Valve
Assembly)
35 to 250°F (2 to 121°C);
15 psig (103 kPa) Saturated Steam
Acoustic Noise 35 dB(A) Maximum at 39 in. (100 cm) per
DIN 1946 and ISO 3745
Agency Compliance All Models UL 873 Listed, File E27734, CCN XAPX;
CSA C22.2 No. 139 Certified, File LR85083, Class 3221 02;
CE Mark, EMC Directive 89/336/EEC
VA-4233-xGC
Models Only
Low Voltage Directive 73/23/EEC
Enclosure Rating NEMA 2, IP 42
Shipping Weight 3.1 lb (1.4 kg)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication
or misuse of its products.
Controls Group
507 E. Michigan Street
P.O. Box 423 Printed in U.S.A.
Milwaukee, WI 53201 www.johnsoncontrols.com