User Guide
Table Of Contents
- Features and Benefits
- Application Overview
- Valve Sizing
- V46 Flowcharts
- Dimensions
- Table 1: Commercial Service V46 Threaded Connection Dimensions
- Table 2: Commercial Service: V46 Flange Connection Dimensions
- Table 3: Maritime Service: ASME Flange Connection Dimensions
- Table 4: Navy “BuShips” Service: Navy Flange Connection Dimensions
- Mounting Adjustment
- Table 5: Range Adjustment Screw
- Manual Flushing
- Companion Flanges and Gaskets
- Repair Data
- Ordering Information
- Table 6: Companion Flange Kits
- Product Number Selection
- Table 7: Type Number Selection Matrix Table 8: Pressure Connection Styles
- Options
- Capillary Tubing Length
- Mounting Bracket
- Table 9: Direct- Acting Commercial Type - Non- corrosive Refrigerants
- Table 10: Commercial Type - Ammonia
- Table 11: Reverse Acting Commercial Type - Non- corrosive Refrigerants
- Table 12: Maritime Type - Non- corrosive Refrigerants
- Table 13: Navy Type - Non- corrosive Refrigerants
- Table 14: Pressure Range Specifications
- Specifications
V46 Series Pressure-Actuated Water-Regulating Valves Product/Technical Bulletin 15
Table 14: Pressure Range Specifications
Refrigerant Maximum Opening
Point psig (kPa)*
Modulation Start
Point
psig (kPa)*
Maximum Permissible Pressure psig (kPa)
V46A, B, C, D V46N Water Refrigerant
All Range
R12, R22,
R134a,
R502, R404a,
R507
70 to 260
(483 to 1793)
90 to 280 (621 to 1931)
40 to 100 (276 to 690)**
150 (1034) 320 (2206)
All Range
with High
Overpressure
70 to 260
(483 to 1793)
___________
150 (1034) 370 (2551)
3/8 in.
Extended
All Range
70 to 300
(483 to 2068)
___________
150 (1034) 440 (3034)
2 and 2-1/2 in.
Low Range
R12, R134a
70 to 170
(483 to 1172)
100 to 200
(690 to 1379)
150 (1034) 230 (1586)
2 and 2-1/2 in.
High Range
R22, R502,
R404a, R507
160 to 260
(1103 to 1793)
180 to 280
(1241 to 1931)
150 (1034) 320 (2206)
Ammonia
R717
100 to 200
(690 to 1379)
130 to 230
(896 to 1586)
150 (1034) 320 (2206)
* V46A, B, C direct acting valve ranges indicate the valve opening point,
V46N reverse acting valve ranges indicates the modulation start point.
** For heat pump applications (3/8 in. through 1-1/2 in. sizes only).