Submittal Sheet

The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls shall not be liable for damages resulting from misapplication or misuse of its products. © 2018 Johnson Controls.
www.johnsoncontrols.com
1
V-3766, V-3966, and V-4332 Brass Pneumatic Flare Valves, 1/2 in. Two-Way and
Three-Way
Code No. LIT-1924115
Issued December 2018
Brass Pneumatic Flare Valves
Description
The 1/2 in. flared valve line accurately
regulates the flow of hot or cold water in small
HVAC terminal units. These 1/2 in. valves are
available with a factory-installed V-3000-1
exposed type pneumatic actuator; enclosed
actuators (V-3000-2) are also available (order
separately). This valve style is available for
field mounting the VA-805x Series electric
actuators or with a factory-coupled
VA-805x Series electric actuator.
Refer to the Flare Valves 1/2 in. Two-Way and
Three-Way Product Bulletin (LIT-977175) for
important product application information.
Features
1/2 in. OD SAE 45 flare connections do not
require solder installation with copper
tubing; provides easy removal for
maintenance
standard Johnson Controls®
non-adjustable ring pack packings provide
proven reliability and long life
body rated 400 psig static pressure does
not restrict building location
every valve tested for tight initial and
long-term shutoff; ensures occupant
comfort and energy conservation
factory-assembled valves available with
pneumatic or electric actuators; install
quickly and easily, minimizing job site time
Selection Charts
Pneumatically Actuated V-3766, V-3966, and V-4332 Flare Valves
Valve
Body
Style
1
1. Normally Open (N.O.); Normally Closed (N.C.); Mixing Valve (MIX); maximum
closeoff pressure (N.C. port/N.O. port)
Max.
Cv
Range-
ability
2
2. Rangeability is defined as the ratio of maximum flow to minimum controllable flow.
Valve Suffix with V-3000 Actuator
(Maximum Closeoff Pressure, psi
3
)
3. Maximum closeoff pressures listed are for 20 psi supply pressure to diaphragm for
normally open and 0 psi supply pressure to diaphragm for normally closed.
Spring Ranges, psi
3 to 6 4 to 8 9 to 13
V-3766 N.O. 1.0 7:1 -1001 (345)
N.O. 1.7 12:1 -1002 (345)
N.O. 3.2 23:1 -1003 (345)
V-3966 N.C. 1.7 12:1 -1001 (240)
N.C. 3.2 23:1 -1002 (240)
V-4332 MIX 1.2 7:1 -1007 (240/240) -1004 (240/240)
MIX 2.0 12:1 -1009 (240/240) -1006 (240/240)
Valid Code Numbers of V-3766, V-3966, and V-4332
Flare Valve and Pneumatic Actuator Combinations
Valid Pneumatic Valve/Actuator
Assembly Code Number
Spring
Range, psi
Max.
Cv
Style
V-3766-1001
V-3766-1002
V-3766-1003
3 to 6
3 to 6
3 to 6
1.0
1.7
3.2
N.O.
V-3966-1001
V-3966-1002
9 to 13
9 to 13
1.7
3.2
N.C.
V-4332-1004
V-4332-1006
V-4332-1007
V-4332-1009
9 to 13
9 to 13
4 to 8
4 to 8
1.2
2.0
1.2
2.0
MIX
VB-3766-1
VB-3766-2
VB-3766-3
None
None
None
1.0
1.7
3.2
PDTC
1
1. Push-Down-to-Close (PDTC); Push-Down-to-Open (PDTO)
VB-3966-1
VB-3966-2
None
None
1.7
3.2
PDTO
1
VB-4332-4
VB-4332-5
None
None
1.2
2.0
MIX
Electrically Actuated VB-3766, VB-3966, and VB-4332 Flare Valves
Valve Body Style Max.Cv Range-ability
VB-3766-1 PDTC 1.0 7:1
VB-3766-2 PDTC 1.7 12:1
VB-3766-3 PDTC 3.2 23:1
VB-4332-4 MIX 1.2 7:1
VB-4332-5 MIX 2.0 12:1
Valid Code Numbers of VB-3766, VB-3966, and VB-4332
Flare Valve and Electric Actuator Combinations
Actuator Valve Body Max. Cv Flared Valve
Body Style
VA-8050-1
Floating/
Incremental
VB-3766-1 1.0 Two-Way PDTC
VB-3766-2 1.7
VB-3766-3 3.2
VB-4332-4 1.2 Three-Way MIX
VB-4332-5 2.0
VA-8051-1
Floating/
Incremental
Feedback
VB-3766-1 1.0 Two-Way PDTC
VB-3766-2 1.7
VB-3766-3 3.2
VB-4332-4 1.2 Three-Way MIX
VA-8050-1 VB-4332-5 2.0
Accessories
Code Number Description
V-3000-8003 Enclosed V-3000 Actuator for Field Mounting
V-3000-10 Valve Position Indicator for V-3000-1 Exposed Style Pneumatically Actuated Valves
V-9502-15 Valve Positioner for Field Mounting to a V-3000-1 Exposed Style Pneumatically Actuated Valve
V-9502-20 Valve Positioner Spring for V-3000-1 Exposed Style Pneumatically Actuated Valves Using a V-9502-15 Positioner; 3.0 psi (21 kPa) Span
V-9502-101 Valve Positioner Spring for V-3000-1 Exposed Style Pneumatically Actuated Valves Using a V-9502-15 Positioner; 4.3 psi (30 kPa) Span
V-9502-19 Valve Positioner Spring for V-3000-1 Exposed Style Pneumatically Actuated Valves Using a V-9502-15 Positioner 8.0 psi (56 kPa) Span
This product can expose you to chemicals
including lead, which is known to the State
of California to cause cancer, birth defects,
or other reproductive harm. For more infor-
mation, go to www.P65Warnings.ca.gov.

Summary of content (2 pages)