Product Overview

4 V-2410 Product Bulletin
Mounting
The V-2410 can be mounted in a
variety of ways depending on
the model ordered. All models
feature two mounting holes on
the bottom of the unit for surface
mounting using two #10-32
screws (field supplied).
In addition, the V-2410-1, -2, -3,
-4, -5, -6, and -7 feature an
integral bracket for wall or panel
mounting using two #8 screws
(field supplied). These models
also feature a conduit
connection should the
application require it.
!
CAUTION: All conduit
housing style V-2410s are
furnished with a ground
wire; however, if this style
of solenoid is to be
grounded via the conduit,
make sure that metallic
conduit is used to
conform with electrical
code requirements.
The V-2410-8 and V-2410-9
(yoke style models featuring
push-on spade terminals) are
shipped with a separate
mounting bracket which can be
attached to the valve base using
the two furnished #10-32
screws. The valve and bracket
assembly can then be mounted
to the surface using two #10
screws (field supplied).
Regardless of the mounting
method chosen, all models can
be installed in any position
without affecting the operation of
the unit. Refer to Figs. 3 and 4
for space requirements and
additional mounting details.
!
CAUTION: Where system
closure, improper flow, or
loss of pressure due to
valve failure can result in
personal injury and/or
loss of property, it is
recommended that
additional devices be
added to indicate proper
system operation (for
example, blade position
indication on damper
blades in smoke control
applications).
When the V-2410 is used in
smoke control applications, it
is recommended that the
solenoid be mounted in an
upright position as close to
the actuator as possible to
provide quick response.
Repair Information
Field repairs must not be made.
For a replacement V-2410,
contact the nearest Johnson
Controls branch office.
Application and Drawing
Identification
Controls Group
507 E. Michigan Street
P.O. Box 423 Printed in U.S.A.
Milwaukee, WI 53202