Supply Fan Runtime—The TEC3000 supports setting runtime limits on the supply fan command. When the
limit is exceeded, an alarm turns on. This feature is intended to be used as a maintenance reminder. Setting
the runtime limit to 0 disables this feature.
Supply Air Temperature Diagnostics—The TEC3000 supports diagnostics when you installed a Supply Air
Temperature. The TEC3000 monitors the supply air. If you call for cooling or heating and the temperature does
not fall or rise by at least the supply air temperature alarm offset value within the supply air temperature alarm
delay, an alarm is generated. If the monitoring occurs while cooling, a cooling ineffective alarm is generated. If
the monitoring occurs while heating, a heating ineffective alarm is generated. If you set the supply air
temperature offset value set to 0, this alarm is disabled.
Zone Temperature Alarm—When enabled, the user can set a low and high temperature alarm; and if the zone
temperature rises or falls below those limits, an alarm is generated.
Trends—Built-in trends exist for many of the inputs and outputs for the TEC3000. These trends are viewable at
the TEC. The analog graph displays data in 15-minute increments over the previous 24 hours or a table with
the last 25 data points. Binary trends display 25 samples taken at every change of state.
Menus and submenus
In Table 13, the * indicates that the menus depend on your configuration.
Table 13: Menus and submenus (Part 1 of 6)
Level 1 Level 2
(LCD screen name)
Setpoints Occupied Cooling
Occupied Heating
Unoccupied Cooling
Unoccupied Heating
Standby Cooling
Standby Heating
Dehumidification*
Occ Setpoint Select
Heat Cool Setpoint Mode
Max Heating Setpoint*
Min Heating Setpoint*
Max Cooling Setpoint*
Min Cooling Setpoint*
Max Setpoint*
Min Setpoint*
Scheduling Schedule Options
Set Schedule
Optimal Start Enable
Temp Occ Duration
Motion Sensor Timeout
Manual Occupancy Mode
Schedule Source