Install Instructions

Table Of Contents
TEC3000 Series Networked and Wireless On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers
with Dehumidification Capability Installation Guide
24
9. Press BACnet Instance ID.
10. Enter the unique BACnet® instance ID using the keypad. This value should be different to the other controllers
on the site.
11. Press Save.
12. Press the back arrow to return to the previous screen.
13. Press BACnet Address.
14. Enter the BACnet MS/TP address through the keypad.
15. Press Save.
16. After selecting N2 in Step 6, press Save.
17. Press the back arrow to return to the previous screen.
18. Press N2 Address.
19. Enter the N2 address through the keypad.
20. Press Save.
Configuring the network settings for wireless models
1. Ensure the TEC screen is on.
2. Press the Menu icon.
3. Press Setup.
4. Press Network Setup.
5. Press FC Comm Mode and the Wireless Field Bus appears. This setting cannot be changed.
6. Press the back arrow to return to the previous screen.
7. Press BACnet Instance ID.
8. Enter the BACnet® instance ID using the keypad. This value should be different to the other controllers on the
site.
9. Press Save.
10. Press the back arrow to return to the previous screen.
11. Press BACnet Address.
12. Enter the BACnet address using the keypad. This value should be different to the other controllers on the PAN.
13. Press Save.
14. Press the back arrow to return to the previous screen.
15. Press PAN ID.
16. Enter the PAN ID using the keypad. This value needs to be the same as set in the associated ZFR Pro
Coordinator Radio.
Once the PAN is set, the TEC attempts to connect to the wireless network. Provided that other devices on the
PAN are in radio range, the connection should occur within one minute. It can then take up to 10 minutes for
the WNC gateway to display that the device is online.
17. Press Save.