Install Instructions
Table Of Contents
- Applications
- North American Emissions Compliance
- United States
- Canada
- Installation
- Parts Included
- Location Considerations
- Installing the Thermostat Controller
- Wiring
- Setup and Adjustments
- Overview
- Customizing the Home Screen
- Touchscreen Icons
- User Lockout
- Using the USB Port
- Loading the Firmware
- Backing Up the Settings
- Restoring the Settings
- Choosing the Communication Mode (TEC3620-00-000, TEC3621-00-000, TEC3622-00-000, and TEC3623-00-000 Models)
- Configuring the Thermostat Controller
- Installer Configuration Menu
- Screen Reset
- Selecting the Unit Type
- By default, the thermostat controller is configured for 4-pipe fan coil mode. To change to a 2-pipe or Pressure-Dependent VAV mode:
- Configuring the Supply Fan - Fan Coil Only
- Setting the Control Mode
- Setting the Fan Mode - Fan Coil Only
- Configuring the Zone Space or Equipment Size
- Changeover
- Dehumidification Control - Fan Coil Only
- Temperature Setpoints
- Configuring Occupancy
- Selecting Schedule Source
- Scheduling
- Setting the Local Schedule
- Overriding the Occupancy Mode
- Enabling Optimal Start
- Enabling the Motion Sensor (TEC3x21-00-000, TEC3x23-00-000 Models)
- PID/PRAC+ Automatic Control Tuning
- Configurable Binary Inputs
- Aux Control
- Commissioning Mode
- Sensor Priority
- Available Fault Diagnostics
- Menus and Submenus
- Troubleshooting
- Repair Information
- TEC3000 Series Proportional Fan Coil and Individual Zone Thermostat Controllers with Dehumidification Capability (Part 1 of 2)
TEC3000 Series Proportional Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
10
Note: VAV and 2-pipe systems should connect their valve to the heating output.
Figure 8: Proportional 0 to 10 VDC Control (Pressure-Dependent VAV)
Figure 9: Proportional 0 to 10 VDC Control
(Pressure-Dependent VAV with Changeover Sensor/Switch)
Figure 10: Proportional 0 to 10 VDC Control
(Pressure-Dependent VAV with Changeover Sensor/Switch and Reheat)
Note: Power to the AUX contact comes from the reheat coil.
Room Temperature Control Thermostat
(Minimum and Maximum Position
Adjusted on Actuator)
Proportional
Actuator
FIG:model_2_clng_only
0 to 10
VDC
COS
COM
HTG
FIG:model_2_htng_clng_chngvr
Changeover
Sensor
Room Temperature Control Thermostat
(Minimum and Maximum Position
Adjusted on Actuator)
Proportional
Actuator
Supply Air
Temperature Sensor
0 to 10
VDC
COS
24V
HTG
FIG:model_2_htng_clng_chngvr_rht
Changeover
Sensor
Room Temperature Control Thermostat
(Minimum and Maximum Position
Adjusted on Actuator)
Heating/Cooling
and On/Off
Duct Heater
Proportional
Actuator
Supply Air
Temperature Sensor
1
C
0 to 10
VDC
COS
COM
24V
HTG
AUX*
AUX*
*The Reheat Installed parameter
must be set to True.