Install Instructions

Table Of Contents
TEC3000 Series Networked and Wireless On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers
with Dehumidification Capability Installation Guide
34
5. Select the days to which the schedule should apply. Note that if events are already set for the selected days,
they appear in the corresponding event box. If any events conflict between selected days, an asterisk appears
in the event box. See Figure 23.
6. Select the Occupancy Status icon for the event. See Figure 24.
Figure 23: Selecting the days
Figure 24: Setting the room occupancy mode
7. Select the Time Set button. See Figure 25.
8. Set the time to the time at which the event will occur and press Save. The screen resets to the Event Set
Schedule screen.
Figure 25: Selecting the time set button (left) and setting the event time (right)
9. Press Save to save the completed event or Trash to delete the completed event. See Figure 26. The screen
resets to the Event 1 Set Schedule screen.
IMPORTANT: Internally, the TEC3000 uses a BACnet schedule where daily schedules are independent of the
previous and next days. The default occupancy of the TEC3000 from the factory is set to Occupied. As a result,
a daily event at 12:00 AM must be scheduled if you do not want the controller to transition to Occupied Mode at
midnight.