Install Instructions
Table Of Contents
- Applications
- North American emissions compliance
- United States
- Canada
- Installation
- Parts included
- Location considerations
- Installing the thermostat controller
- Wiring
- Setup and adjustments
- Overview
- Customizing the home screen
- Touchscreen icons
- User lockout
- Using the USB port
- Loading the firmware
- Backing up the settings
- Restoring the settings
- Choosing the Communication mode (TEC3612 and TEC3613 Models)
- Configuring the network settings for wireless models
- Configuring the thermostat controller
- Installer configuration menu
- Screen reset
- Selecting the unit type
- By default, the thermostat controller is configured for four-pipe fan coil mode. To change to a two-pipe or Pressure-Dependent VAV mode:
- Selecting the heating and cooling device type
- Configuring the supply fan - fan coil only
- Setting the Control mode
- Setting the Fan mode - fan coil only
- Configuring the zone space or equipment size - units configured with floating actuators, multi- speed fans, and variable-speed fans only
- Changeover
- Dehumidification control - fan coil only
- Temperature setpoints
- Configuring occupancy
- Selecting schedule source
- Scheduling (for networked models)
- Setting the local schedule
- Overriding the Occupancy mode
- Enabling optimal start
- Enabling the motion sensor (TEC3x12, TEC3x13 Models)
- PID/PRAC+ automatic control tuning
- Configurable binary inputs
- Aux control
- Commissioning mode
- Configurable analog inputs (AIs)
- Configuring the AIs
- Networked sensors
- Availability of AIs
- Priority for configurable AIs
- Priority for overall sensors data sources
- Available fault diagnostics
- Menus and submenus
- Troubleshooting
- Repair information
- Technical specifications
- TEC3000 Series Networked and Wireless On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification Capability (Part 1 of 3)
TEC3000 Series Networked and Wireless On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers
with Dehumidification Capability Installation Guide
28
The following Fan Override options are provided for multi-speed fans:
• Low—Fan is continuously on low
• Medium—Fan is continuously on medium
• High—Fan is continuously on high
• Auto—Follows the behavior set as Fan Mode
• Quiet—Follows the behavior set as Fan Mode, but prevents the fan from ever going above minimum speed
To set the Fan Mode:
1. Press the Menu icon.
2. Press Setup.
3. Press General Control Setup.
4. Press Fan Mode and select On, Auto, or Smart.
5. Press Save and the back arrow
to return to the previous screen.
Configuring the zone space or equipment size - units configured with floating actuators, multi-
speed fans, and variable-speed fans only
With non-binary outputs, the TEC3000 is configured by default to have a slower temperature response for larger
zones with normal-sized equipment. In installations with small zones and oversized equipment, set the Equipment
Size parameter to Oversized.
To set the Equipment Size parameter:
1. Press the Menu icon.
2. Press Control Setup.
3. Press Tuning.
4. Use the up and down arrows to navigate to Equipment Size.
5. Press Equipment Setup and select Oversized.
6. Press Save and the back arrow
to return to the previous screen.
Changeover
Pressure-Dependent VAV systems and two-pipe fan coils require changeover detection in order to switch seasonal
operation between heating and cooling modes. The TEC supports the following methods for changeover:
automatic changeover using an analog sensor (thermistor), automatic changeover using a binary switch, or remote
changeover from a BAS and manual changeover.
For automatic changeover, a supply temperature sensor or switch must be connected to the Changeover Sensor
(COS) input of the TEC. Changeover Mode must be set to Auto, and Supply Temp Type must be set for Analog
Sensor, Cooling N.C. (cooling when switch is closed), or Heating N.C. (heating when switch is closed). When an
analog sensor is used, the changeover setpoint can be adjusted. The changeover logic applies a 10-degree
Fahrenheit differential to the setpoint. The system switches to cooling mode when the temperature drops below the
changeover setpoint and remains in cooling mode until the measured temperature has risen 10 degrees above the
changeover setpoint.
To configure automatic changeover:
1. Press the Menu icon.
2. Press Setup.
3. Press Equipment Setup.
4. Press Changeover.