Install Instructions
Table Of Contents
- Applications
 - North American emissions compliance
 - United States
 - Canada
 - Installation
 - Parts included
 - Location considerations
 - Installing the thermostat controller
 - Wiring
 - Setup and adjustments
 - Overview
 - Customizing the home screen
 - Touchscreen icons
 - User lockout
 - Using the USB port
 - Loading the firmware
 - Backing up the settings
 - Restoring the settings
 - Choosing the Communication mode (TEC3612 and TEC3613 Models)
 - Configuring the network settings for wireless models
 - Configuring the thermostat controller
 - Installer configuration menu
 - Screen reset
 - Selecting the unit type
 - By default, the thermostat controller is configured for four-pipe fan coil mode. To change to a two-pipe or Pressure-Dependent VAV mode:
 - Selecting the heating and cooling device type
 - Configuring the supply fan - fan coil only
 - Setting the Control mode
 - Setting the Fan mode - fan coil only
 - Configuring the zone space or equipment size - units configured with floating actuators, multi- speed fans, and variable-speed fans only
 - Changeover
 - Dehumidification control - fan coil only
 - Temperature setpoints
 - Configuring occupancy
 - Selecting schedule source
 - Scheduling (for networked models)
 - Setting the local schedule
 - Overriding the Occupancy mode
 - Enabling optimal start
 - Enabling the motion sensor (TEC3x12, TEC3x13 Models)
 - PID/PRAC+ automatic control tuning
 - Configurable binary inputs
 - Aux control
 - Commissioning mode
 - Configurable analog inputs (AIs)
 - Configuring the AIs
 - Networked sensors
 - Availability of AIs
 - Priority for configurable AIs
 - Priority for overall sensors data sources
 - Available fault diagnostics
 - Menus and submenus
 - Troubleshooting
 - Repair information
 - Technical specifications
 - TEC3000 Series Networked and Wireless On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification Capability (Part 1 of 3)
 
TEC3000 Series Networked and Wireless On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers 
with Dehumidification Capability Installation Guide
10
Table 4:  Terminal identification (See Figure 7, Figure 8, and Figure 9 for wiring diagrams)
Terminal label Function
TEC3012, TEC3013 
Floating FC/VAV and On/
Off FC
1
TEC3312, TEC3313 Floating 
FC/VAV and On/Off FC
1
TEC3612, TEC3613 
Floating FC/VAV and On/Off 
FC
1
24 V 24 VAC hot from transformer
FAN H Fan high
FAN M Fan medium
FAN L Fan on (single-speed, variable-speed), Fan low (multi-speed)
AUX Auxiliary binary output
AUX Auxiliary power
COM
2
24 VAC common from transformer
COM
2
24 VAC common from transformer
CLG O Cool open (Floating), Cooling NC (On/Off), Triac
CLG C Cool close (Floating), Cooling NO (On/Off), Triac
HTG O Heat open (Floating), Heating NC (On/Off), Triac
HTG C Heat close (Floating), Heating NO (On/Off), Triac
RSEN Configurable analog input 1
COS Configurable analog input 2/Changeover binary switch input
VSF Variable speed fan command (configurable 0 to 10 V range)
BI-2 Configurable binary input 2
BI-1 Configurable binary input 1
NET+ N/A Not connected Field bus+/N2+
NET- N/A Not connected Field bus-/N2-
NET COM N/A Not connected Isolated common for field bus
1. There is no support for an On and Off VAV.
2. COM on TB1 must be jumpered to COM on TB2.










