Auxiliary output rating/triac
output
19 to 30 VAC, 1.0 A maximum, 15 mA minimum, 3.0 A in-rush
Binary inputs Dry contact across terminal COM to terminals BI1, BI2, or COS
Analog inputs Nickel, platinum, A99B, 2.25k ohm NTC, 10k ohm NTC, 10k ohm NTC Type 3 across
terminal COM to terminals R SEN or COS
Temperature sensor type Local digital sensor
Wire size 18 AWG (1.0 mm diameter) maximum, 22 AWG (0.6 mm diameter) recommended
MS/TP network guidelines For wired models: Up to 100 devices maximum for each Network Automation Engine
(NAE); 4,000 ft (1,219 m) maximum cable length. Refer to the MS/TP Technical
Bulletin for the Metasys, FX, or Verasys® system installed.
For wireless models: Up to 100 devices maximum for each Network Automation
Engine (NAE)
Wireless band (for wireless
models)
Direct-sequence spread-spectrum 2.4 GHz ISM bands
Transmission power (for wireless
models)
10 mW maximum
Transmission range (for wireless
models)
50 ft (15.2 m) recommended indoor
250 ft (76.2 m) line of sight, maximum
Temperature
range
Backlit display -40.0°F/-40.0°C to 122.0°F/50.0°C in 0.5° increments
Heating control 40.0°F/4.5°C to 90.0°F/32.0°C
Cooling control 54.0°F/12.0°C to 100.0°F/38.0°C
Accuracy Temperature ±0.9F°/±0.5C° at 70.0°F/21.0°C typical calibrated
Humidity ±5% RH from 20 to 80% RH at 50°F to 90°F (10°C to 32°C)
Minimum deadband 2F°/1C° between heating and cooling
Occupancy sensor motion
detection (occupancy sensing
models)
Minimum of 94 angular degrees up to a distance of 15 ft (4.6 m);
based on a clear line of sight
Ambient
conditions
Operating 32°F to 122°F (0°C to 50°C); 95% RH maximum, noncondensing
Storage -22°F to 122°F (-30°C to 50°C); 95% RH maximum, noncondensing
Compliance BACnet
International
BACnet Testing Laboratories™ (BTL) 135-2001 Listed BACnet Advanced Application
Controller (B-AAC)
United States UL Listed, File E27734, CCN XAPX, Under UL60730
Networked models: FCC Compliant to CFR 47, Part 15, Subpart B, Class B
Wireless models: Transmission complies with FCC Part 15.247 regulations for low
power unlicensed transmitters; transmitter identification FCC: OEJ-WRZRADIO
Canada UL Listed, File E27734, CCN XAPX7, Under E60730
Networked models: Industry Canada, ICES-003
Wireless models: Industry Canada (IC) RSS-210;
Transmitter identification ZFR1810-1: IC: 279A-WRZRADIO
Europe (for
networked
models only)
CE Mark – Johnson Controls declares that this product is in compliance
with the essential requirements and other relevant provisions of the EMC Directive
and the RoHS Directive.
Australia and
New Zealand
RCM Mark, Australia/NZ Emissions Compliant
TEC3000 Series Networked and Wireless On/Off or Floating Fan Coil and Individual Zone