Install Instructions
Table Of Contents
- Applications
- North American emissions compliance
- United States
- Canada
- Installation
- Parts included
- Location considerations
- Installing the thermostat controller
- Wiring
- Setup and adjustments
- Overview
- Customizing the home screen
- Touchscreen icons
- User lockout
- Using the USB port
- Loading the firmware
- Backing up the settings
- Restoring the settings
- Choosing the Communication mode (TEC3612 and TEC3613 Models)
- Configuring the network settings for wireless models
- Configuring the thermostat controller
- Installer configuration menu
- Screen reset
- Selecting the unit type
- By default, the thermostat controller is configured for four-pipe fan coil mode. To change to a two-pipe or Pressure-Dependent VAV mode:
- Selecting the heating and cooling device type
- Configuring the supply fan - fan coil only
- Setting the Control mode
- Setting the Fan mode - fan coil only
- Configuring the zone space or equipment size - units configured with floating actuators, multi- speed fans, and variable-speed fans only
- Changeover
- Dehumidification control - fan coil only
- Temperature setpoints
- Configuring occupancy
- Selecting schedule source
- Scheduling (for networked models)
- Setting the local schedule
- Overriding the Occupancy mode
- Enabling optimal start
- Enabling the motion sensor (TEC3x12, TEC3x13 Models)
- PID/PRAC+ automatic control tuning
- Configurable binary inputs
- Aux control
- Commissioning mode
- Configurable analog inputs (AIs)
- Configuring the AIs
- Networked sensors
- Availability of AIs
- Priority for configurable AIs
- Priority for overall sensors data sources
- Available fault diagnostics
- Menus and submenus
- Troubleshooting
- Repair information
- Technical specifications
- TEC3000 Series Networked and Wireless On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification Capability (Part 1 of 3)
TEC3000 Series Networked and Wireless On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers
with Dehumidification Capability Installation Guide
31
Configuring occupancy
To adapt to nearly any application, the TEC3000 controller supports a wide variety of occupancy sources, such as:
• Local stand-alone weekly scheduler
• Remote schedule from BAS
• Occupancy sensor (internal or remote)
• Occupancy binary input (configurable)
• Manual occupancy override
• Temporary occupancy (by interacting with the screen while in unoccupied mode)
• Temporary occupancy binary input
Occupancy is determined using a top-down decision matrix as shown in Table 8.
Occ Setpoint Select =
Setpoint Offset and
Heat Cool Setpoint Mode =
Common Setpoint
In this mode, the TEC has one setpoint, Common Setpoint, for heating and cooling. There is
also a common Setpoint Offset (warmer/cooler adjust) that is only applied to Common
Setpoint. Otherwise, this setting works the same as when Occ Setpoint Select = Setpoint
Offset and Heat Cool Setpoint Mode = Individual Setpoints.
Occ Setpoint Select = Min
and Max Setpoints and
Heat Cool Setpoint Mode =
Common Setpoint
In this mode, the TEC has one setpoint, Common Setpoint, for heating and cooling. There is
a configurable range for Common Setpoint, Min Setpoint, and Max Setpoint.
Table 7: Setpoint operation
Mode of setpoint
operation
Details