Away from steam or water pipes, warm air stacks, unconditioned areas (not heated or cooled), or sources of
electrical interference
In a clear path between the integrated passive infrared (PIR) occupancy sensor (if equipped) and the space
being monitored
For wireless models, also locate the thermostat controller:
Outside of a recessed area, metal enclosure, or shelving unit
On the same building level as the other wireless devices on the same personal area network (PAN)
At least 2 in. (51 mm) away from any metal obstruction
In the direct line of sight to other wireless devices on the same PAN. Signal transmission is best if the path
between the TEC3000 and other wireless devices is direct as possible. Line of sight is desirable but not
required. See Table 1 for recommended and maximum distances.
Away from metal and large solid obstructions (including equipment rooms and elevator shafts and concrete or
brick walls) between the TEC3000 and the ZFR Pro Router/Repeater or ZFR Pro Coordinator Radio
Within range of two or more wireless devices on the same PAN. Redundancy in the layout provides the best
reliability in wireless installations
At least 20 ft (6 m) from a microwave oven
For integrated PIR models, be sure that the thermostat controller is located centrally, where occupant movement is
frequent. Ensure that the unit is not blocked by a plastic tamper resistant enclosure (such as the GRD10A-608).
The plastic enclosure blocks the occupancy sensing capability.
The use of insulating foam pads is required for installations where wiring passes through the wall to the thermostat.
For wireless models, the effective transmission range and distance for indoor applications vary because of wireless
signal absorption and reflection due to metal obstructions, walls or floors, and furniture found in typical building
interiors.
Notes:
Allow for sufficient clearance to insert a USB drive into the USB port
For more details on using ZFR Pro Series communication devices, refer to the WNC1800/ZFR182x Pro
Series Wireless Field Bus System Technical Bulletin (LIT-12012356).
Table 1: Indoor line-of-sight transmission ranges
Range type Transmission distance
WNC Coordinator Radio,
ZFR Pro Repeater
TEC3000 Wireless Thermostat
Controller
Recommended 50 ft (15.2 m) 50 ft (15.2 m)
Line of sight, maximum 250 ft (76.2 m) 100 ft (30 m)
IMPORTANT: Only connect memory devices to the USB port. Do not use it for charging external devices.