User Guide
Table Of Contents
TE-6300P Series Temperature Sensors Installation Instructions 1
Applications
To meet plenum rating where Underwriters
Laboratories Inc.® UL 1995 rating is accepted, replace
the existing thermoplastic cover with the TE-6001-13
Metal Cover. To meet International Mechanical Code
standards, use all-metal components.
Installation
Dimensions
Table 1: TE-6300P Applications
Duct Probe Temperature Sensor
Model Description and Probe, in. (mm)
TE-6311P-1 1k ohm Thin-Film Nickel, 8 (203)
TE-6351P-1 1k ohm Thin-Film Platinum, 8 (203)
TE-6341P-1 2.2k ohm Negative Temperature
Coefficient (NTC) Thermistor, 8 (203)
TE-6361P-1 10k ohm Type II, NTC Thermistor, 8 (203)
Well Insertion Temperature Sensor
Model Description and Probe, in. (mm)
TE-6312P-1 1k ohm Thin-Film Nickel, 8 (203)
TE-631AP-1 1k ohm Thin-Film Nickel, 6 (152)
TE-6352P-1 1k ohm Thin-Film Platinum, 8 (203)
TE-635AP-1 1k ohm Thin-Film Platinum, 6 (152)
TE-6342P-1 2.2k ohm NTC Thermistor, 8 (203)
Duct Averaging Temperature Sensor
Model Description and Probe, in. (mm)
TE-6315P-1 1k ohm Nickel Wire, 8 (2.4)
TE-6316P-1 1k ohm Nickel Wire, 17 (5.2)
TE-6327P-1 1k ohm Platinum Equivalent Wire, 10
(3.0)
TE-6328P-1 1k ohm Platinum Equivalent Wire, 20
(6.1)
TE-6337P-1 100 ohm Platinum Equivalent Wire, 10
(3.0)
TE-6338P-1 100 ohm Platinum Equivalent Wire, 20
(6.1)
IMPORTANT: The TE-6300P Series Temperature
Sensors are intended to provide an input to
equipment under normal operating conditions.
Where failure or malfunction of the sensor could
lead to personal injury or property damage to the
controlled equipment or other property, additional
precautions must be designed into the control
system. Incorporate and maintain other devices
such as supervisory or alarm systems or safety or
limit controls intended to warn of, or protect against,
failure or malfunction of the sensor.
IMPORTANT: Do not install the TE-6300P Series
Temperature Sensor probe in ambient temperatures
beyond the specified 50 to 220°F (46 to 104°C)
temperature range. Installing the temperature
sensor probe in ambient temperatures beyond this
range may damage the unit and void the warranty.
Figure 1: Duct Probe Sensor Dimensions, in. (mm)
1/2-14 NPT Threads
F
I
G
:
6
3
0
0
_
d
i
m
TE-6300P Series Temperature Sensors
Installation Instructions
TE-63xxP-1
Part No. 24-4034-107, Rev. H
Issued April 6, 2010