Wiring
For 1k ohm nickel temperature sensors, wire resistance can
cause about 1F° (0.56C°) of error for every 250 ft (76 m) run
of 18 AWG (1.0 mm diameter) wire, or every 100 ft (31 m) run
of 22 AWG (0.6 mm diameter) wire. For 1k ohm platinum
temperature sensors, wire resistance can cause about
1F° (0.56C°) of error for every 150 ft (46 m) run of 18 AWG
(1.0 mm diameter) wire, or every 50 ft (15 m) run of 22 AWG
(0.6 mm diameter) wire. To minimize error due to field wiring,
limit total resistance of all nickel temperature sensor wiring to
3 ohms, and all platinum temperature sensor wiring to
2 ohms.
The 2.2k and 10k ohm thermistor applications permit wiring
to be relatively long before wire resistance adds significantly
to total resistance measured at the controller. As a general
rule, a 150 ft (46 m) two-wire 18 AWG (1.0 mm diameter) run
contributes 2 ohms of error, or less than 1F° (0.56C°) error
over the sensor operating temperature range.
Refer to the appropriate controller documentation for
recommended sensor wiring. Secure the wiring bushing or
conduit only to the temperature sensor base. See Table 1 for
an explanation of the lead wiring color convention
Repair Information
I
f the TE-6300M Series Well Insertion Temperature Sensor fails
to operate within its specifications, replace the unit. For a
replacement sensor, contact the nearest Johnson Controls
representative.
Technical Specifications
Table 1: Lead Wiring Color Code
Sensor Type Lead Color
1k ohm Nickel White
1k ohm Platinum White with Blue Stripe
2.2k or 10k ohm Thermistor White with Green Stripe
IMPORTANT: Make all wiring connections in
accordance with local, national, and regional regulations
.
TE-6300M Series Well Insertion Temperature Sensors
Models TE-631xM Thin-Film Nickel Temperature Sensor
TE-632xM Thin-Film Platinum Temperature Sensor
TE-634xM 2.2k ohm Thermistor Temperature Sensor
TE-636xM 10k ohm Thermistor Temperature Sensor
Sensor Reference Resistance Nickel 1k ohms at 70°F (21°C)
Platinum 1k ohms at 32°F (0°C)
2.2k ohm Thermistor 2,252 ohms at 77°F (25°C)
10k ohm Thermistor 10k ohms at 77°F (25°C)
Sensor Accuracy Nickel ±0.34F° at 70°F (±0.19C° at 21°C)
Platinum ±0.73F° at 70°F (±0.41C° at 21°C), DIN Class B
2.2k ohm Thermistor ±0.36F° (±0.2C°) in the Range 32 to 158°F (0 to 70°C)
10k ohm Thermistor ±0.9F° (±0.5C°) in the Range 32 to 158°F (0 to 70°C)
Sensor Temperature
Coefficient
Nickel Approximately 3 ohms/F° (5.4 ohms/C°)
Platinum Approximately 2 ohms/F° (3.9 ohms/C°)
2.2k ohm Thermistor Nonlinear, Negative Temperature Coefficient (NTC)
10k ohm Thermistor Nonlinear, NTC, Johnson Controls Type II
Electrical Connections 22 AWG (0.6 mm Diameter) x 6 in. (150 mm) Long Lead Wires
Materials Well Adaptor 0.875 in. (22.2 mm) Hex Brass
Probe 0.25 in. (6.4 mm) Outside Diameter x 5 in. (127 mm) or 8 in. (203 mm)
Long Stainless Steel
Enclosure Corrosion-Resistant Steel
Operating Conditions Temperature -50 to 220°F (-46 to 104°C)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the
local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.