TE-6300P Series Temperature Sensors
Sensor Reference
Resistance
1k ohm Thin-Film Nickel 1k ohms at 70°F (21°C)
1k ohm Nickel Averaging 1k ohms at 70°F (21°C)
1k ohm Thin-Film Platinum 1k ohms at 32°F (0°C)
100 ohm Platinum Averaging 100 ohms at 32°F (0°C)
1k ohm Platinum Averaging 1k ohms at 32°F (0°C)
2.2k ohm Thermistor 2,252 ohms at 77°F (25°C)
10k ohm Thermistor 10k ohms at 77°F (25°C)
Sensor Accuracy 1k ohm Thin-Film Nickel ± 0.34F° at 70°F (± 0.19C° at 21°C)
1k ohm Nickel Averaging ± 3.4F° at 70°F (± 1.9C° at 21°C),
1k ohm Thin-Film Platinum ± 0.35F° at 70°F (± 0.19C° at 21°C), DIN Class A
100 ohm Platinum Averaging ± 1.0F° at 70°F (± 058C° at 21°C)
1k ohm Platinum Averaging ± 1.0F° at 70°F (± 058C° at 21°C)
2.2k ohm Thermistor ± 0.36F° (± 0.2C°) in the range: 32 to 158°F (0 to 70°C)
10k ohm Thermistor ± 0.9F° (±0.5C°) in the range: 32 to 158°F (0 to 70°C)
Sensor Temperature
Coefficient
1k ohm Thin-Film Nickel Approximately 3 ohms/F° (5.4 ohms/C°)
1k ohm Nickel Averaging Approximately 3 ohms/F° (5.4 ohms/C°)
1k ohm Thin-Film Platinum Approximately 2 ohms/F° (3.9 ohms/C°) 3,850 ppm/K
100 ohm Platinum Averaging Approximately 0.2 ohms/F° (.39 ohms/C°)
1k ohm Platinum Averaging Approximately 2 ohms/F° (3.9 ohms/C°)
2.2k ohm Thermistor Nonlinear, Negative Temperature Coefficient (NTC)
10k ohm Thermistor
Nonlinear, NTC, Johnson Controls
®
Type II
Materials Probe .25 in. (6.4 mm) Outside Diameter (O.D.) x 6 in. (152 mm) or 8 in.
(203 mm) Long, Stainless Steel Tubing
Nickel Averaging Probe 0.094 in. (2.4 mm) O.D. x8 ft (2.4 m) or 17 ft (5.2 m) Long,
Copper Tubing
Platinum Averaging Probe 0.19 in. (4.8 mm) O.D. x 10 ft (3.0 m) or 20 ft (6.1 m) Long,
Aluminum Tubing
Conduit Box Rigid Thermoplastic
Sensor Holder Rigid Thermoplastic
Mounting Plate Aluminum
Operating Conditions Probe Assembly -50 to 220°F (-46 to 104°C)
Conduit Box -50 to 122°F (-46 to 50°C)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication
or misuse of its products.