For 1k ohm nickel temperature sensors, wire 
resistance can cause approximately 1F° (0.56C°) of 
error for every 250 ft (76 m) run of 18 AWG wire, or 
every 100 ft (31 m) run of 22 AWG wire. For 1k ohm 
platinum temperature sensors, wire resistance can 
cause approximately 1F° (0.56C°) of error for every 
150 ft (46 m) run of 18 AWG wire, or every 50 ft (15 m) 
run of 22 AWG wire. To minimize error due to field 
wiring, limit the total resistance of all nickel temperature 
sensor wiring to 3 ohms, and all 1k ohm platinum 
temperature sensor wiring to 2 ohms.
To minimize wiring error in applications using 100 ohm 
platinum equivalent sensors, use the TQ-6000-1, 4 
to 20 mA transmitter. Using a 4 wire (Kelvin) 
connection can also eliminate wiring error.
The 2.2k and 10k ohm thermistor applications permit 
wiring to be relatively long before wire resistance adds 
significantly to total resistance measured at the 
controller. As a general rule, a 150 ft (46 m) two-wire 18 
AWG run contributes 2 ohms of error, or less than 1F° 
(0.56C°) error over the sensor operating temperature 
range.
Refer to the appropriate controller documentation for 
recommended sensor wiring. See Table 2 for an 
explanation of the lead wiring color convention.
Series-Parallel Wiring
To wire a duct averaging sensor, or another model in 
series-parallel configuration, see Figure 11.
Note: Always use sensors of the same value and type 
throughout the network.
Repair Information
If the TE-6300P Series Temperature Sensor fails to 
operate within its specifications, refer to the 
TE-6300 Series Temperature Sensor Product Bulletin 
(LIT-216320) for a list of repair parts available.
Table 2:  Lead Wiring (22 AWG, 6 in.) Color Code
Sensor Type Lead Color
1k ohm Nickel White
1k ohm Nickel Averaging
1
1. Nickel Averaging sensors use 18 AWG wire
White
100 ohm Platinum Averaging Red
1k ohm Platinum White with blue strip
1k ohm Platinum Averaging Blue
2.2k ohm Thermistor Red
10k ohm Thermistor White with green stripe
Figure 11: Series-Parallel Wiring Network
Four Sensors
F
i
g
:
w
r
n
g
!
CAUTION: Risk of Property Damage.
Do not apply power to the system before 
checking all wiring connections. Short 
circuited or improperly connected wires 
may result in permanent damage to the 
equipment.
IMPORTANT: Use copper conductors only. Make 
all wiring connections in accordance with local, 
national, and regional regulations. Do not exceed 
the TE-6300P Series Temperature Sensor’s 
electrical ratings.