Install Instructions
Table Of Contents
TE-6300P Series Temperature Sensors Installation Instructions4
Mounting the Well Insertion Sensor
The TE-63xxP-1 well models include a sensor holder 
with built-in thermowell adaptor. No additional well 
adaptor is required for installation when the sensor is 
used with TE-6300W thermowells. See Figure 8 and 
mount the sensor as follows:
Note: Add thermal grease (F-1000-182, or equivalent) 
before inserting the probe if the well does not include 
thermal grease. For proper sensor function, mount the 
well so that any condensation that forms drains out of 
the probe.
1. Remove the sensor holder from the conduit box 
(See Securing or Removing the Sensor Holder
 on 
page 2).
2. Loosen the sensor holder setscrew and remove the 
probe.
3. If the thermal well is:
• TE-6300W-103 (TE-63xAP-1), see Figure 9 
and loosen the two well set screws (the 
TE-6300W-103 contains thermal grease). 
Insert the sensor holder, then tighten the well 
set screws.
• TE-6300W-110 (TE-63x2P-1), see Figure 10 
and screw the sensor holder into the thermal 
well (the TE-6300W-110 does not contain 
thermal grease).
4. Insert the sensor probe through the sensor holder 
and into the thermal well until it just touches the 
bottom of the well.
5. Back the probe out approximately 1/8 in. (3 mm) 
and tighten the sensor holder set screw.
6. Pull the sensor wires into the conduit box and snap 
the conduit box onto the sensor holder.
7. Install the retainer over the sensor wire leads and 
into the sensor holder.
8. Wire the sensor to the controller using the wire nuts 
provided.
9. Reposition the cover and tighten the retention 
screws.
Figure 8: Installing the Well Insertion Sensor
(Included, 
assembled
to Conduit Box)
Conduit Box
(Included)
Figure 9: Installing the TE-63xAP-1 Sensor Holder
Sensor
Holder
Figure 10: Installing the TE-63x2P-1 Sensor Holder