Install Instructions
Table Of Contents
TE-6300P Series Temperature Sensors Installation Instructions4
Mounting the Well Insertion Sensor
The TE-63xxP-1 well models include a sensor holder
with built-in thermowell adaptor. No additional well
adaptor is required for installation when the sensor is
used with TE-6300W thermowells. See Figure 8 and
mount the sensor as follows:
Note: Add thermal grease (F-1000-182, or equivalent)
before inserting the probe if the well does not include
thermal grease. For proper sensor function, mount the
well so that any condensation that forms drains out of
the probe.
1. Remove the sensor holder from the conduit box
(See Securing or Removing the Sensor Holder
on
page 2).
2. Loosen the sensor holder setscrew and remove the
probe.
3. If the thermal well is:
• TE-6300W-103 (TE-63xAP-1), see Figure 9
and loosen the two well set screws (the
TE-6300W-103 contains thermal grease).
Insert the sensor holder, then tighten the well
set screws.
• TE-6300W-110 (TE-63x2P-1), see Figure 10
and screw the sensor holder into the thermal
well (the TE-6300W-110 does not contain
thermal grease).
4. Insert the sensor probe through the sensor holder
and into the thermal well until it just touches the
bottom of the well.
5. Back the probe out approximately 1/8 in. (3 mm)
and tighten the sensor holder set screw.
6. Pull the sensor wires into the conduit box and snap
the conduit box onto the sensor holder.
7. Install the retainer over the sensor wire leads and
into the sensor holder.
8. Wire the sensor to the controller using the wire nuts
provided.
9. Reposition the cover and tighten the retention
screws.
Figure 8: Installing the Well Insertion Sensor
(Included,
assembled
to Conduit Box)
Conduit Box
(Included)
Figure 9: Installing the TE-63xAP-1 Sensor Holder
Sensor
Holder
Figure 10: Installing the TE-63x2P-1 Sensor Holder