Install Instructions
Table Of Contents
TE-6300P Series Temperature Sensors Installation Instructions 3
To remove the sensor holder from the conduit box, 
slide the retainer off of the sensor probe. Push the snap 
finger toward the center of the sensor holder and pull 
the holder out of the conduit box.
Note: It may be necessary to loosen the set screw 
and remove the sensor probe to obtain adequate 
clearance to slide the sensor holder out of the conduit 
box.
Mounting the Temperature Sensors
Mounting the Duct Sensor
See Figure 5 and mount the sensor as follows:
1. Drill a 1-3/8 in. (35 mm) diameter hole at the 
desired mounting location.
2. Use the mounting plate as a template to drill four
1/8 in. (3 mm) holes for the screws.
3. Mount the probe assembly to the duct using the 
four screws provided.
4. Pull the wires into the conduit box and snap the 
conduit box onto the sensor holder.
5. Install the retainer into the sensor holder.
6. Wire the sensor to the controller using the wire nuts 
provided.
7. Reposition the cover and tighten the retention 
screws.
Mounting the Duct Averaging Sensor
See Figure 6 to mount a single duct averaging sensor. 
See Figure 7 to mount four duct averaging sensors in 
series-parallel for larger ducts. Mount the duct 
averaging sensor as follows:
1. Drill a 1-3/8 in. (35 mm) diameter hole at the 
desired mounting location.
2. Use the mounting plate as a template to drill four
1/8 in. (3 mm) holes for the screws.
3. Mount the averaging sensor probe inside the duct 
using a TE-6001-8 or equivalent 3 in. (76 mm) 
minimum radius temperature element holder.
Note: Platinum sensor models include two TE-6001-8 
Element Holders.
4. Insert the sensor probe into the sensor holder and 
mounting plate assembly. Firmly tighten the sensor 
holder set screw.
5. Follow Steps 3 through 7 in Mounting the Duct 
Sensor.
Figure 6: Installing the Duct Averaging Sensor
IMPORTANT: Do not bend the sensor probe tighter 
than a 3 in. (76 mm) radius, a 6 in. (152 mm) 
diameter, to avoid permanently damaging the 
sensor.