Product Overview

Series Y63, Y64, Y65, Y66, and Y69 Transformers Product Bulletin 1
The Series Y63, Y64, Y65, Y66, and Y69 Transformers
provide 24 VAC power for loads of 40 VA through 300
VA. These transformers are designed for use on digital
controllers, gas controls, ignition systems, motor
actuators, staging controls, and most other 24 VAC
Heating, Ventilation, Air Conditioning, and
Refrigeration (HVACR) control systems.
The Y6x Series meets the requirements of UL 1585,
UL 506, and CSA C22.2 No. 66, providing compliance
in both the United States and Canada. The Y63, Y64,
Y65, and Y66 transformers are listed as Class 2
transformers (UL 1585, CSA C22.2 No. 66). The Y69 is
listed as a general purpose transformer (UL 506, CSA
C22.2 No. 66).
Selecting a Transformer
See Table 2 to select the appropriate transformer for
your application.
Note: All conduit fittings are 1/2-14 National Pipe
Straight Threads (NPSTs). Performance and dimension
specifications are nominal and are subject to accepted
manufacturing tolerances and applications.
Figure 1: Model Y65T31-0 Transformer
Table 1: Features and Benefits
Features Benefits
Split-Bobbin Design Provides best primary/secondary isolation.
Multi-Tap Primaries Reduce stocking requirements and offers application flexibility.
Choice of Foot, Plate, or Conduit Hub
Mounting
Provides mounting flexibility.
Choice of Primary Voltages Meets a wide range of power requirements from 24 VAC through 480 VAC.
Color-Coded Lead Wires Provide simplicity and standardization.
cULus Listed or cURus Recognized Meets US and Canadian requirements for Class 2 transformers (Y63, Y64, Y65,
and Y66) and general purpose transformers (Y69).
Built-In, Easy-Reset Circuit Breakers Eliminate replacement time and cost caused by burnout (Y63, Y64, Y66, and Y69).
Open Frame Y65 Models Serve as ideal models when end bells are not required.
IMPORTANT: The new line of transformers does
not offer exact replacements for older styles. Some
dimensions and voltages have changed. The VA
rating for 100 VA transformers has changed to
92 VA to comply with UL 1585.
Series Y63, Y64, Y65, Y66, and Y69 Transformers
Product Bulletin
Code No. LIT-125755
Issued July 16, 2009
Supersedes December 17, 2002

Summary of content (6 pages)