4 TE-6000 Series Temperature Sensing Elements Installation Instructions
Repairs and Replacement
Do not field repair the TE-6000 temperature sensing
elements. To order a replacement, refer to the
TE-6000 Series Temperature Sensing Elements
Product Bulletin (LIT-216288).
Technical Specifications
Product
TE-6000-1 1,000 ohm nickel element
TE-6000-2 500 ohm nickel element
TE-6000-3 333 ohm nickel element
TE-6000-5 50 ohm nickel element
TE-6000-6 1,000 ohm nickel (used in solar heating applications)
TE-6000-10 1,000 ohm nickel surface element (encased in aluminum mounting
block)
TE-6000-11 1,000 ohm nickel bearing element (encased in a brass tube)
TE-6000-100 1,000 ohm nickel wide range element
TE-6000-101 1,000 ohm nickel narrow range element
TE-6359-1 1,000 ohm platinum element
Sensing Ranges
TE-6000-6: -40 to 350°F (-40 to 177°C)
TE-6000-10: 0 to 125°F (-18 to 52°C)
All Other Models: -50 to 250
°
F (-46 to 121
°
C)
Elements
TE-6359-1: Platinum
All other models: Nickel
Resistance Tolerances
TE-6000-1, -2, -3, -6, -10, -11:
±1.0%
TE-6000-5: ±2.0%
TE-6000-100: ±0.1%, range of -50 to 250°F (-46 to 121°C)
TE-6000-101: ±0.1%, range of 55 to 85°F (13 to 29°C)
TE-6359-1:
±0.06% (platinum, DIN Class A)
Temperature Coefficients
(All Positive and
Approximate)
Nickel: 0.15, 1.0, 1.5 and 3 ohms/F° (0.27,1.8, 2.7, and 5.4 ohms/C°)
for 50, 333.3, 500, and 1,000 ohm elements respectively
Platinum:
2.2 ohms/F° (3.9 ohms/C°)
Reference Resistance
At 32°F (0°C) TE-6359-1: 1,000 ohms (platinum)
At 70°F (21°C) TE-6000-1, 6, 10, 11, 100, 101: 1,000 ohms (nickel)
TE-6000-2: 500 ohms (nickel)
TE-6000-3: 333 ohms (nickel)
TE-6000-5: 50 ohms (nickel)
Temperature Ranges
TE-6000-6: -40 to 350°F (-40 to 177°C)
TE-6000-10: 0 to 125°F (-18 to 52°C)
TE-6000-101: 55 to 85°F (13 to 29°C)
All other models: -50 to 250
°
F (-46 to 121
°
C)
Sensor Construction
TE-6000-6: Black Anodized Aluminum Probe
TE-6000-10: Aluminum Probe
TE-6000-11: Brass Probe
All Other Models: Copper Probe
Field Connection
Two wire leads, 18 AWG
Shipping Weight
0.2 lb (0.09 kg)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or
misuse of its products.