T26 Series Line Voltage Thermostats Product/Technical Bulletin 5
1 2
h
Line
Neutral
3
Heating and Cooling
H° °C H° °C
To Heating
Load
To Cooling
Load
Manual or Automatic
Changeover Switch
Figure 9: T26S, T26T Wired for Heating and Cooling
with Manual or Automatic Changeover Switch
1
h
Line
Neutral
Heating and Cooling
Y
B
R
Fan Speed Control
(if used)
Fan
Valve
Changeover Control
3
2
Figure 10: T26S, T26T on Fan Coil Unit with
Cycling Valve and Continuous Fan (Terminal
markings shown for A19CAC changeover control.)
1
h
Line
Neutral
Heating and Cooling
Y
B
R
Fan Speed Control
(if used)
Fan
Valve
Changeover Control
2
3
Figure 11: T26S, T26T on Fan Coil Unit with
Cycling Fan and Valve (Terminal markings shown
for A19CAC changeover control.)
Table 1: Electrical Ratings
T26A, T26S
Motor Ratings 120V 208V 240V 277V
AC Full Load Ampere 6.0 3.5 3.0 --
AC Locked Rotor
Ampere
36.0 21.0 18.0 --
AC Non-inductive
Ampere
10.0 10.0 10.0 10.0
Pilot Duty - 125 VA, 24 to 277 VAC
T26B and Heating Side of T26T
AC Full Load Ampere 16.0 9.2 8.0 --
AC Locked Rotor
Ampere
96.0 55.2 48.0 --
AC Non-inductive
Ampere
22.0 22.0 22.0 22.0
Pilot Duty - 125 VA, 24 to 277 VAC
Cooling Side of T26T
AC Full Load Ampere 8.0 8.0 8.0
AC Locked Rotor
Ampere
48.0 48.0 48.0
Pilot Duty - 125 VA, 24 to 277 VAC
T26J
AC Full Load Ampere 6.0 3.5 3.0
AC Locked Rotor
Ampere
36.0 21.0 18.0
Pilot Duty - 125 VA, 24 to 277 VAC
A
djustments
For concealed dial models (with cover removed), the
desired dial setting should be lined up with the
reference mark on the base of the thermostat.
(See Figure 12.) This will place the desired setting at
the 9 o’clock position when the thermostat is held
vertically.
Range Stops
High and low range stops can be field adjusted as
desired. Use the following procedures to set the high
and low range stops.
Note: Energy conservation models have a fixed
factory-set limited range. The stops are not
field adjustable.