Product Overview
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2011 Johnson Controls, Inc.
www.johnsoncontrols.com
T-4600
Energy Manager Heating-Cooling Low Volume Output Thermostat
Description
The T-4600 Thermostat is a low volume
output, energy managing, heating-cooling
thermostat. The independent setpoints can
result in a deadband to encourage energy
conservation by eliminating heating and
cooling overlap.
Refer to T-4000 Series Pneumatic Room
Thermostat Product Bulletin (LIT-7171060P)
for important product information.
Repair Information
If the T-4600 Energy Manager Heating-
Cooling Low Volume Output Thermostat fails
to operate within its specifications, replace the
unit. For a replacement thermostat, contact
the nearest Johnson Controls®
representative.
Selection Charts
T-4600 Thermostat
Code Number Description
T-4600-1 Direct Acting, Fahrenheit
T-4600-2 Reverse Acting, Fahrenheit
T-4600-3 Direct Acting, Celsius
T-4600-5 Direct and Reverse, Fahrenheit
T-4600-6 Direct and Reverse, Celsius
Accessories for T-4600
Code Number Description
R-3710 Series
(two required)
0.005 or 0.007 inch Restrictors
Technical Specifications
T-4600 Energy Manager Heating-Cooling LOw Volume Output Thermostat
Sensitivity Adjustable from 1 to 3 psig/°F (12 to 38 kPa/°C)
Factory set at approximately 2.5 psig/°F (32 kPa/°C)
Flow Capacity 45 SCIM (12 mL/s) with .007 in. Restrictor
25 SCIM (7 mL/s) with .005 in. Restrictor
Air Consumption 50 SCIM (14 mL/s) or 90 SCIM (24 mL/s) depending on Restrictor
Supply Pressure 13 to 25 psig (91 to 175 kPa)
Nominal 20 psig (140 kPa)
Dial Range 55 to 85°F or 12 to 28°C
Air Connections Two Restricted Supply/Output for Heating and Cooling
Code No. LIT-1921705
Issued January 15, 2008
T-4600 Energy Manager Heating-Cooling
Low Volume Output Thermostat
Features
• mounts vertically
• available in Fahrenheit or Celsius models
• two outputs
• adjustable sensitivities
• adjustable set points
• available in these models
- Dual Direct
- Dual Reverse
- Direct and Reverse