Install Instructions
Table Of Contents
Figure 2: Removing the Sensor Cover
PCB
Locking Tab
Figure 3: Opening the Sensor PCB
Figure 4: Mounting the Sensor Base
Wiring
!
CAUTION: Risk of Electrical Shock.
Disconnect power supply before making electrical
connections to avoid electrical shock.
Note:
Note:
Keep sensor conductors as short as possible
to minimize temperature error. If necessary, the indoor
temperature displayed at the thermostat can be
adjusted (see the appropriate T600 or TEC2100
Installation Instructions).
To complete wiring for the sensor:
1. Connect wires between the T600 or TEC2100
thermostat and the SEN-600-1 or SEN-600-4
sensors according to the appropriate wiring
diagram (see Figure 5).
2. Set the switch on the PCB in the remote indoor
sensor to the correct positions (see Table 1 for
switch positions).
3. Reattach the sensor cover to the installed base
(top side first) and install the security screw on the
bottom.
4. Verify that the sensor is functioning by checking
the temperature display on the T600 or TEC2100
thermostat. If using the SEN-600-4 remote sensor,
verify the functionality of the override button and
occupancy status LED.
If using the SEN-600-4, the digital input on the
thermostat to which the D1 terminal on the sensor is
connected must be configured for remote override
(RemOVR). See the T600 Installation Instructions for
details on configuring the digital input.
!
CAUTION: Risk of Electrical Shock.
Do not apply power to the system before checking
all wiring connections. Short circuited or improperly
connected wires may result in permanent damage to
the equipment.
Table 1: Switch Positions for Single or Multiple
Sensor Installations
Number of Sensors Switch 1 Switch 2
1 Sensor
On On
2 Sensor
Off On
3 Sensor
Off Off
2 SEN-600-1 and SEN-600-4 Remote Indoor Temperature Sensors Installation Instructions