Product Overview
Table Of Contents
Armored
Sleeve
Capillary
Tube
Breakaway
Schrader Valve
Depressor
Flare Nut
SEC99_02
Figure 2: Removing the Schrader Valve Depressor
Repairs and Replacement
Do not attempt to repair a damaged SEC99 UltraCap
or UltraTube. Contact the nearest
Johnson Controls/Penn® representative to obtain a
replacement.
Table 1: SEC99 Series Dimensions and Physical Features Selection Matrix
Series First
Letter
Fitting Type and Internal
Capillary/Tube Diameter
Second
Letter
First Tube Angle and
Depressor
Second Tube Angle and
Depressor
SEC99
A 1/4 in. SAE Female Flare with a 0.06 in.
(1.5 mm) Internal Diameter Capillary
A Straight, with Depressor Straight, without Depressor
B 1/4 in. SAE Female Flare with a 0.2 in.
(5 mm) Internal Diameter Tube
B Straight, with Depressor 90 Deg, with Depressor
C Straight, with Depressor 90 Deg without Depressor
D Straight, without Depressor 90 Deg, without Depressor
E Straight, without Depressor Straight, without Depressor
F 90 Deg, without Depressor 90 Deg, without Depressor
Technical Specifications
Product
SEC99A UltraCap /SEC99B UltraTube
Materials
SEC99A: Forged brass nut with copper stem
SEC99B: Silver-color plated forged brass nut with copper stem
Style
1/4 in. SAE female flare connector with break-away Schrader valve depressor
(depending on type selected)
Fittings
Shape
Straight or 90° elbow
Outside
SEC99A 0.125 in. (3.1 mm), SEC99B 0.250 in. (6.3 mm)
Capillary
Diameter
Inside
SEC99A 0.06 in. (1.5 mm), SEC99B 0.2 in. (5 mm)
Ambient Operating Conditions
-50 to 300°F (-46 to 149°C), 95% RH
Maximum Working Pressure
690 psig (4757 kPa)
Burst Pressure
3450 psig (23,786 kPa)
Suggested Torque to Seal
8 to 10 lb·ft (10.9 to 13.6 N·m)
Compliance
UL Recognized: File SA9457, CCN SFCS2
UL Recognized for Canada: SA9457, CCN SFCS8
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult Johnson Controls/PENN Application Engineering at 1-800-275-5676. Johnson Controls, Inc. shall not be liable for
damages resulting from misapplication or misuse of its products.
Controls Group
507 E. Michigan Street
P.O. Box 423 Published in U.S.A.
www.johnsoncontrols.com
Milwaukee, WI 53201
2 SEC99A UltraCap Armored Capillary and SEC99B UltraTube Armored Tubing Installation Instructions