Inc. Air Conditioner User Manual

505430-BTG-A-0309
Johnson Controls Unitary Products 73
Electrical Data - Outdoor Unit - HP Without Powered Convenience Outlet
Model
Compressors Outdoor Fan Motor
Pwr Conv
Outlet
Minimum
Circuit
Ampacity
1
Maximum
Fuse Size
(A)
2
Power
Supply
Qty.
RLA
(each)
MCC
(each)
LRA
(each)
Qty
FLA
(each)
FLA
PH-07
208/230-3-60 1 25.0 39 164 2 2.1 0.0 35.5 45
460-3-60 1 12.2 19 100 2 1.2 0.0 17.6 25
575-3-60 1 9.0 14 78 2 0.9 0.0 13.1 20
PH-10
208/230-3-60 2 15.6 24 110 2 3.0 0.0 41.2 50
460-3-60 2 7.8 12 52 2 1.6 0.0 20.8 25
575-3-60 2 5.8 9 39 2 1.4 0.0 15.8 20
PH-15
208/230-3-60 2 25.0 39 164 4 2.1 0.0 64.7 80
460-3-60 2 12.2 19 100 4 1.2 0.0 32.2 40
575-3-60 2 9.0 14 78 4 0.9 0.0 24.0 30
PJ-15
208/230-3-60 2 25.0 39 164 4 2.1 0.0 64.7 80
460-3-60 2 12.2 19 100 4 1.2 0.0 32.2 40
575-3-60 2 9.0 14 78 4 0.9 0.0 24.0 30
PH-20
208/230-3-60 2 30.1 47 225 4 3.0 0.0 79.8 100
460-3-60 2 16.7 26 114 4 1.6 0.0 44.0 60
575-3-60 2 12.2 19 80 4 1.4 0.0 32.9 45
PJ-20
208/230-3-60 2 30.1 47 225 4 3.0 0.0 79.8 100
460-3-60 2 16.7 26 114 4 1.6 0.0 44.0 60
575-3-60 2 12.2 19 80 4 1.4 0.0 32.9 45
1
Based on three, 75°C insulated copper conductors in conduit and ambient of 30°C.
2
Maximum fuse or maximum circuit breaker (HACR type per NEC).
Refer to NEC/NFPA No. 70, Articles 440-11, 12 for information on minimum disconnect sizing.
Electrical Data - Outdoor Unit - HP With Powered Convenience Outlet
Model
Compressors Outdoor Fan Motor
Pwr Conv
Outlet
Minimum
Circuit
Ampacity
1
Maximum
Fuse Size
(A)
2
Power
Supply
Qty.
RLA
(each)
MCC
(each)
LRA
(each)
Qty
FLA
(each)
FLA
PH-07
208/230-3-60 1 25.0 39 164 2 2.1 10.0 45.5 60
460-3-60 1 12.2 19 100 2 1.2 5.0 22.6 30
575-3-60 1 9.0 14 78 2 0.9 4.0 17.1 25
PH-10
208/230-3-60 2 15.6 24 110 2 3.0 10.0 51.2 60
460-3-60 2 7.8 12 52 2 1.6 5.0 25.8 30
575-3-60 2 5.8 9 39 2 1.4 4.0 19.8 25
PH-15
208/230-3-60 2 25.0 39 164 4 2.1 10.0 74.7 90
460-3-60 2 12.2 19 100 4 1.2 5.0 37.2 45
575-3-60 2 9.0 14 78 4 0.9 4.0 28.0 35
PJ-15
208/230-3-60 2 25.0 39 164 4 2.1 10.0 74.7 90
460-3-60 2 12.2 19 100 4 1.2 5.0 37.2 45
575-3-60 2 9.0 14 78 4 0.9 4.0 28.0 35
PH-20
208/230-3-60 2 30.1 47 225 4 3.0 10.0 89.8 110
460-3-60 2 16.7 28 114 4 1.6 5.0 49.0 60
575-3-60 2 12.2 19 80 4 1.4 4.0 36.9 45
PJ-20
208/230-3-60 2 30.1 47 225 4 3.0 10.0 89.8 110
460-3-60 2 16.7 26 114 4 1.6 5.0 49.0 60
575-3-60 2 12.2 19 80 4 1.4 4.0 36.9 45
1
Based on three, 75°C insulated copper conductors in conduit and ambient of 30°C.
2
Maximum fuse or maximum circuit breaker (HACR type per NEC).
Refer to NEC/NFPA No. 70, Articles 440-11, 12 for information on minimum disconnect sizing.