Electrical Data - Outdoor Unit - AC With Powered Convenience Outlet
Model
Compressors Outdoor Fan Motor
Pwr Conv
Outlet
Minimum
Circuit
Ampacity
1
Maximum
Fuse Size
(A)
2
Power
Supply
Qty.
RLA
(each)
MCC
(each)
LRA
(each)
Qty
FLA
(each)
FLA
YH-07
208/230-3-60 1 25.0 39 164 2 2.1 10.0 45.5 60
460-3-60 1 12.2 19 100 2 1.2 5.0 22.6 30
575-3-60 1 9.0 14 78 2 0.9 4.0 17.1 25
YH-10
208/230-3-60 2 15.6 24 110 2 3.0 10.0 51.2 60
460-3-60 2 7.8 12 52 2 1.6 5.0 25.8 30
575-3-60 2 5.8 9 39 2 1.4 4.0 19.8 25
YJ-10
208/230-3-60 2 17.3 27 123 2 3.0 10.0 55.0 70
460-3-60 2 9.6 15 70 2 1.6 5.0 29.8 35
575-3-60 2 7.7 12 53 2 1.4 4.0 24.0 30
YH-12
208/230-3-60 2 22.4 35 149 2 3.0 10.0 66.5 80
460-3-60 2 10.6 17 75 2 1.6 5.0 32.1 40
575-3-60 2 7.7 12 54 2 1.4 4.0 24.0 30
YJ-12
208/230-3-60 2 23.1 36 160 2 3.0 10.0 68.0 90
460-3-60 2 12.2 19 87 2 1.6 5.0 35.7 45
575-3-60 2 8.7 14 62 2 1.4 4.0 26.3 30
YH-15
208/230-3-60 2 25.0 39 164 4 2.1 10.0 74.7 90
460-3-60 2 12.2 19 100 4 1.2 5.0 37.2 45
575-3-60 2 9.0 14 78 4 0.9 4.0 28.0 35
YJ-15
208/230-3-60 2 25.0 39 164 4 2.1 10.0 74.7 90
460-3-60 2 12.2 19 100 4 1.2 5.0 37.2 45
575-3-60 2 9.0 14 78 4 0.9 4.0 28.0 35
YH-20
208/230-3-60 2 30.1 47 225 4 3.0 10.0 89.8 110
460-3-60 2 16.7 26 114 4 1.6 5.0 49.0 60
575-3-60 2 12.2 19 80 4 1.4 4.0 36.9 45
YJ-20
208/230-3-60 2 30.1 47 225 4 3.0 10.0 89.8 110
460-3-60 2 16.7 26 114 4 1.6 5.0 49.0 60
575-3-60 2 12.2 19 80 4 1.4 4.0 36.9 45
1
Based on three, 75°C insulated copper conductors in conduit and ambient of 30°C.
2
Maximum fuse or maximum circuit breaker (HACR type per NEC).
Refer to NEC/NFPA No. 70, Articles 440-11, 12 for information on minimum disconnect sizing.