RPM Selection
Unit Model HP Max BHP Motor Sheave Blower Sheave
6 Turns
Open
5 Turns
Open
4 Turns
Open
3 Turns
Open
2 Turns
Open
1 Turn
Open
Fully
Closed
NH-07
Std. 1.5 1.73 1VL40 AK69 N/A 690 743 796 849 902 955
HS 2 2.30 1VL40 AK56 N/A 863 929 995 1062 1128 1194
NH/NJ-10
Std. 2 2.30 1VL40 AK74 N/A 641 690 739 789 838 887
HS 3 3.45 1VP56 AK84 N/A 906 949 992 1035 1078 1121
NH/NJ-15
Std. 3 3.45 1VP50 AK114 N/A 565 596 627 659 690 721
HS 5 5.75 2VP50 2B5V94 707 745 782 819 856 894 N/A
NH/NJ-20
Std. 5 5.75 2VP50 2B5V94 686 722 758 794 830 866 N/A
HS 7.5 8.63 2VP65 2B5V94 925 960 996 1031 1067 1103 1138