P499 Series Electronic Pressure Transducers Product/Technical Bulletin  5
3. Measure the current between the transducer 
SUPPLY (red wire) and COMMON (black wire) with 
a multimeter set to measure milliamperes (mA). 
This is the measured output current.
4. Compare the ideal output current (Step 2) to the 
measured output current (Step 3). If the current 
from measured output current differs greatly from 
the ideal output current, replace the transducer. 
Note: It is normal for the transducer reading to differ 
somewhat from pressure gauge readings due to 
multimeter and gauge tolerances, and other factors.
Repair Information
Do not attempt to repair or recalibrate the P499 Series 
Electronic Pressure Transducers. If repair or 
replacement is needed, contact your nearest 
Johnson Controls/PENN authorized distributor or sales 
representative.
Ordering
Figure 6 is a type identification matrix that identifies all 
the potential P499 Series electronic pressure 
transducer types. Not all combinations in Figure 6 are 
manufactured and available. Contact your local 
Johnson Controls/PENN representative for more 
information on options available for high-volume 
models with specific application requirements.
Table 3 through Table 5 list the features on standard 
P499 transducer models available through most 
Johnson Controls/PENN authorized distributors.
See Table 2 for information on wire harnesses. 
Figure 6: P499 Series Electronic Pressure Transducer Type Identification Matrix
Transducer Base Number
P499
Output Signal
A 
B 
C
R
V
 4 to 20 mA
 0 to 5 VDC
 1 to 5 VDC
 0.5 to 4.5 VDC 
 0 to 10 VDC
Ratiometric
Pressure Connection
A
B
C
D
E
F
G
 1/8”-27 NPT External Thread (Style 49)
 1/4” SAE 45  Flare External Thread 
 1/4” SAE   (7/16-20 UNF) with Depressor 
 1/4”-18 NPT 
 1/2”-20 UNF-2A SAE  with O-ring
 1/4”-18 NPTF 
 M16 x 1.5 Ermeto 
o
45  Flare Internal Thread (Style 47)
External Thread
External Thread 
External Thread
External Thread
o
Electrical Connection
A
C
H
J
P
S
 AMP (compatible with 174357-2 and 174358-7 connectors)
 Cable - Unshielded
 Hirschmann Form C with mating cable socket (DIN43650)
 Packard
 Cable - Shielded
Hirschmann Form A without mating cable socket (DIN43650)
Pressure Range
101 
102 
105 
107 
0-100 PSI
0-200 PSI
0-500 PSI
0-750 PSI
Packaging
C
D 
K
 Individual
 Bulk
 Kit: transducer, cable, and literature
F
I
G
:
o
r
d
r
_
m
t
r
x
Pressure Mode
- 
A
S
Gauge
 Absolute (0.75% Accuracy)
 Sealed Gauge   (0.75% Accuracy)