Product Overview
Table Of Contents
P499 Series Electronic Pressure Transducers Product/Technical Bulletin4
Checkout
Before applying power, check all wiring connections. 
After applying power, operate controlled equipment 
under normal conditions and use a reliable set of 
pressure gauges to verify that the transducer and the 
associated control are operating properly.
0.5 to 4.5 VDC Ratiometric Versions
The ratiometric versions of the P499 transducer 
receive a constant 5 VDC (nominal) supply voltage and 
vary the output signal voltage, based on the sensed 
pressure. The output voltage varies from 10% to 90% 
of the supply voltage, providing a 0.5 to 4.5 VDC 
(nominal) signal.
To verify that the transducer is working properly:
1. With the transducer in place and the controlled 
system pressure stabilized, measure the pressure 
at the transducer with an accurate and reliable 
gauge. Use this in Step 3 as the measured 
pressure, P.
2. Measure the voltage between SUPPLY (red wire) 
and COMMON (black wire). Use this in Step 3 as 
the measured supply voltage, Vs.
3. Use the equation in Figure 3 to calculate the ideal 
output voltage for the ratiometric transducers. 
4. Measure the voltage between the transducer 
OUTPUT (white wire) and COMMON (black wire) 
with a multimeter set to measure DC voltage. This 
is the measured output voltage.
5. Compare the ideal output voltage (Step 3) and the 
measured output voltage (Step 4). If the measured 
output voltage differs greatly from the ideal output 
voltage, replace the transducer. 
Note: It is normal for the transducer reading to differ 
somewhat from pressure gauge readings due to 
voltmeter and gauge tolerances, and other factors.
0 to 10 VDC Versions
To verify that the transducer is working properly:
1. With the transducer in place and the controlled 
system pressure stabilized, measure the pressure 
at the transducer with an accurate and reliable 
gauge. Use this in Step 2 as the measured 
pressure, P.
2. Use the equation in Figure 4 to calculate the ideal 
output voltage for the 0 to 10 VDC transducers.
3. Measure the voltage between the transducer 
OUTPUT (white wire) and COMMON (black wire) 
with a multimeter set to measure DC voltage. This 
is the measured output voltage.
4. Compare the ideal output voltage (Step 2) and the 
measured output voltage (Step 3). If the measured 
output voltage differs greatly from the ideal output 
voltage, replace the transducer.
Note: It is normal for the transducer reading to differ 
somewhat from pressure gauge readings due to 
voltmeter and gauge tolerances, and other factors.
4 to 20 mA Versions
To verify that the transducer is working properly:
1. With the transducer in place and the controlled 
system pressure stabilized, measure the pressure 
at the transducer with an accurate and reliable 
gauge. Use this in Step 2 as the measured 
pressure, P.
2. Use the equation in Figure 5 to calculate the ideal 
output current for the 4 to 20 mA transducers.
IMPORTANT: The P499 transducer is a precision 
sensing device and testing accuracy is typically 
beyond the capability of field diagnostic tools.
Figure 3: Ideal Voltage Calculation for 
0.5 to 4.5 VDC Ratiometric Transducers
P
V
o = Vs [0.1 + 0.8 ( )] VDC
Vo= Ideal Output Voltage
Vs= Measured Supply Voltage
P = Measured Pressure
Px = Full Range Pressure of Sensor
F
I
G
:
i
d
l
_
r
t
m
t
r
c
Figure 4: Ideal Voltage Calculation for 
0 to 10 VDC Transducers
V
o = 10 ( ) VDC
P
Vo= Ideal Output Voltage
P = Measured Pressure
Px = Full Range Pressure of Sensor
F
I
G
:
i
d
l
_
1
0
V
Figure 5: Ideal Current Calculation for 
4-20 mA Transducers
I = 4 + 16 ( ) mA
P
I = Ideal Output Current
P = Measured Pressure
Px = Full Range Pressure of Sensor
F
I
G
:
i
d
l
_
m
A








