Product Overview
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2008 Johnson Controls, Inc.
www.johnsoncontrols.com
1 of 1
P352P Series
Electronic Proportional Plus Integral Pressure Controls:
Static Pressure (W.C.) and PSI Series
Code No. LIT-1922440
Issued November 18, 2008
Description
The P352P Electronic Proportional Plus
Integral Pressure Control Series has two
proportional outputs of 0 to 10 VDC and
0 to 20 mA. Proportional
Plus Integral (PI)
control is an option to hold setpoint, regardless
of load shifts on a system.
Two models cover the pressure ranges of 0.5
to 5 in. W.C. and 0.025 to 0.25 in. W.C., and
use the DPT2640 Pressure Transmitters.
Three models cover the pressure ranges of
0-100 psi, 90-250 psi, and 240-600 psi, and
use the P499 Pressure Transducers. (See
Selection Chart)
. All P352P models can use
the Y350R Power Module.
.
1
2
34
O
N
Integration DIP Switch
(shown in proportional only position
)
Setpoint
Dial
Throttling Range
Potentiometer
Minimum
Output
Potentiometer
(0-10 VDC Output) V
(0-20 mA Output) I
(Sensor) (+) SN
VDC (+5 VDC)
24 V (24 VAC) (+)
Module
Connector
LED Indicator
(Percent of Output)
Direct
Acting
Reverse
Acting
Operation Mode
Jumper Positions
THROT
RANGE
MIN
OUTPU
T
Fast (C1)
Medium (C2)
Slow (C3)
Off
Cover Screws (Quantity = 4)
C (Common) (-)
a350p.eps.eps
Interior of P352P
Features
• field selectable proportional only or
proportional plus integral control
• surface of DIN rail mounting
• ten segment LED displays percent of
output signal
• field selectable reverse/direct acting mode
• minimum output adjustment
• 5-pin connectors eliminate wiring between
modules
Applications
• dual static pressure control
• building pressurization
• condenser fan speed control
• damper positioning
• flow valve positioning
Selection Chart
Code
Number
Output Setpoint
Range
Throttling
Range
Pressure Sensor
(Order Separately)
Sensor Input
Range
Associated Stage and
Display Modules
P352PQ-1C
Proportional Voltage:
0 to 10 VDC
and
Proportional Current:
0 to 20 mA
0.5 to 5 in. W.C. DPT2640-010D 0 to 10 in. W.C. (No Stage Module) D352CA-1C
P352PQ-2C 0.025 to 0.25 in. W.C. DPT2640-0R5D 0 to 0.5 in. W.C. (No Stage Module) D352CA-2C
P352PN-2C 0 - 100 psi 5 - 50 psi P499RAP-101K or P499RCP-101K 0 - 100 psi
S352AA-2C, D352AA-2CP352PN-3C 90 - 250 psi
10 - 100 psi
P499RAP-105K or P499RCP-105K 0 - 500 psi
P352PN-4C 240 - 600 psi P499RAP-107K or P499RCP-107K 0 - 750 psi
Note: Order the pressure sensor separately. If required, power,
stage, and display modules may also be ordered separately.
Technical Specifications
P352P Electronic Proportional Plus
Integral Static Pressure Control
Supply
Voltage
1
1. Only one input voltage source may be used.
Transformer 20 to 30 VAC, 50/60 Hz, Class 2
Y350R 120/240 VAC, 50/60 Hz
Proportional Output 0 to 10 VDC (550 ohm load minimum) and
0 to 20 mA (600 ohm load maximum).
Minimum Output Adjustable to 0 to 60% of full output span
Output Indication A ten segment LED bar graph indicates
percentage of output
Control Action Direct or reverse action is jumper selectable
Power Consumption 3.2 VA
Integration Constant Three selectable rates C1, C2, C3, and Off
position
Ambient
Temperature
Operating -30 to 150°F (-34 to 66°C)
Shipping -40 to 185°F (-40 to 85°C)
Ambient Humidity 0 to 95% RH non-condensing
Case and Cover Material NEMA 1, High-impact thermoplastic
Mounting Slot
for No. 6 Screws
1.20
31
2.40
61
0.42
11
1.56
40
0.145
3.68
DIN Rail
Mount
Condu
it
Hole
0.875
22
P352P
2.94
75
5.00
127
2.40
61
0.85
22
0.5
13
p352p_2.eps.eps
P352P Dimensions, in. (mm)