Product Overview
Table Of Contents
Controls Group 507 E. Michigan Street
P.O. Box 423, Milwaukee, WI 53202
Code No. LIT-1922440
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson
Controls office. Neither Johnson Controls, Inc. nor its subsidiaries or affiliates shall be liable for damages resulting from misapplication or misuse of its products.
© 09/03 Johnson Controls, Inc
1/1
p352ps p;w 1922440 9thcc:na Electric System 350 Rev:
071897
logo:
standard
left ft:
none
right ft:
standard
Sect# = 2
seQ# = 310
p352p.tif
P352P
a350p.eps
1
2
34
O
N
Integration DIP Switch
(shown in proportional only position)
Setpoint
Dial
Throttling Range
Potentiomet er
Minimum
Output
Potentiometer
(0-10 VDC Output) V
(0-20 mA Output) I
(Sensor) (+) SN
VDC (+5 VDC)
24 V (24 VAC) (+)
Module
Connector
LED Indicator
(Percent of Output)
Direct
Acting
Reverse
Acting
Operation Mode
Jumper Positions
THROT
RANGE
MIN
OUTPU
T
Fast (C1)
Medium (C2)
Slow (C3)
Off
Cover Screws (Quantity = 4)
C (Common) (-)
Description
The P352P Electronic Proportional Plus
Integral Pressure Control Series has two
proportional outputs of 0 to 10 VDC and
0 to 20 mA. Proportional plus integral (PI)
control is an option to hold setpoint,
regardless of load shifts on a system.
Two models cover the pressure ranges of 0.5 to
5 in. W.C. and 0.025 to 0.25 in. W.C., and use the
DPT2640 Pressure Transmitters. Three models
cover the pressure ranges of 0-100 psi, 90-250
psi, and 240-600 psi, and use the P399 Pressure
Transducers. (See Selection Chart) All P352P
models can use the Y350R Power Module.
Features
• field selectable proportional only or
proportional plus integral control
• surface of DIN rail mounting
• ten segment LED displays percent of output
signal
• field selectable reverse/direct acting mode
• minimum output adjustment
• 5-pin connectors eliminate wiring between
modules
Applications
• dual static pressure control
• building pressurization
• condenser fan speed control
• damper positioning
• flow valve positioning
To Order
Specify code number from the selection chart
below, along with the corresponding pressure
sensor. If required, power, stage, and display
modules may be ordered separately.
Selection Chart
Specifications
Code
Number
Output
Setpoint
Range
Throttling
Range
Pressure Sensor
(Order Separately)
Sensor Input
Range
Associated Stage and
Display Modules
P352PQ-1C
Proportional Voltage:
0 to 10 VDC
and
Proportional Current:
0 to 20 mA
0.5 to 5 in. W.C. DPT2640-010D 0 to 10 in. W.C. (No Stage Module) D352CA-1C
P352PQ-2C 0.025 to 0.25 in. W.C. DPT2640-0R5D 0 to 0.5 in. W.C. (No Stage Module) D352CA-2C
P352PN-2C 0 - 100 psi 5 - 50 psi P399AAA-1-200C or P399AAC-1-200C 0 - 100 psi
S352AA-2C, D352AA-2CP352PN-3C 90 - 250 psi
10 - 100 psi
P399BAA-1-200C or P399BAC-1-200C 0 - 500 psi
P352PN-4C 240 - 600 psi P399CAA-1-200C or P399CAC-1-200C 0 - 750 psi
P352P Electronic Proportional Plus
Integral Static Pressure Control
Supply
Voltage
(a)
(a) Only one input voltage source may be used.
Transformer 20 to 30 VAC, 50/60 Hz, Class 2
Y350R 120/240 VAC, 50/60 Hz
Proportional Output
0 to 10 VDC (550 ohm load minimum) and
0 to 20 mA (600 ohm load maximum).
Minimum Output Adjustable to 0 to 60% of full output span
Output Indication
A ten segment LED bar graph indicates
percentage of output
Control Action Direct or reverse action is jumper selectable
Power Consumption 3.2 VA
Integration Constant
Three selectable rates C1, C2, C3, and Off
position
Ambient
Temperature
Operating -30 to 150°F (-34 to 66°C)
Shipping -40 to 185°F (-40 to 85°C)
Ambient Humidity 0 to 95% RH non-condensing
Case and Cover Material NEMA 1, High-impact thermoplastic
P352P Dimensions, in. (mm) p352p_2.eps
Mounting Slot
for No. 6 Screws
1.20
31
2.40
61
0.42
11
1.56
40
0.145
3.68
DIN Rail
Mount
Conduit
Hole
0.875
22
P352P
2.94
75
5.00
127
2.40
61
0.85
22
0.5
13
P352P Series
Electronic Proportional Plus Integral Pressure Controls:
Static Pressure (W.C.) and PSI Series