Install Instructions
Table Of Contents
- Application
- Mounting
- Pressure Connections
- Avoid Sharp Bends in the Capillary Tube
- Allow for Slack in the Capillary Tube
- Coil and Secure Excess Capillary Tubing
- Avoid Contact between the Capillary Tubing and Sharp or Abrasive Objects
- Do Not Overtighten Flare Nuts on Pressure Connection Line Fittings
- Avoid Severe Pressure Pulsation at Pressure Connections
- Wiring
- Adjustments
- Technical Specifications
- Especificaciones Técnicas
Electrical Ratings
Table 3: SPST Electrical Ratings (P70A, B, C, D, and P170A, B, C, D Type Models)
Standard Single-Phase Ratings Hermetic Compressor
Single-Phase Ratings
120 VAC 208 VAC 240 VAC *480 VAC *600 VAC 208/240 VAC
Motor Full-Load Amperes
24 18.7 17 5 4.8 24
Motor Locked-Rotor Amperes
144 112.2 102 30 28.8 144
Non-Inductive Amperes
22 22 22 -- -- --
Pilot Duty
125 VA at 120 to 600 VAC; 57.5 VA at 120 to 300 VDC
* Not for compressor motor loads
Table 4: SPDT Electrical Ratings Standard Differential Switch (P70E Type Models)
Standard Single-Phase Ratings
120 VAC 208 VAC 240 VAC 277 VAC*
Motor Full Load Amperes
16.0 9.2 8.0 7.0
Motor Locked Rotor
Amperes
96.0 55.2 48.0 42.0
Non-Inductive Amperes
16.0 16.0 16.0 16.0
Pilot Duty
125 VA at 120 to 600 VAC 125 VA at 24 to 600 VAC
* Rating for P70EC models only
Table 5: 4-Wire, 2-Circuit Electrical Ratings (P70G, H, J, K, and P170K Type Models)
Standard Single-Phase Ratings
Line-M2 (Main Contacts) Line-M1 (Auxiliary Contacts)
120
VAC
208
VAC
240
VAC
277
VAC
*480
VAC
*600
VAC
120
VAC
208
VAC
240
VAC
277
VAC
Motor Full Load
Amperes
16.0 9.2 8.0 -- 5 4.8 6.0 3.3 3.0 --
Motor Locked Rotor
Amperes
96.0 55.2 48.0 -- 30 28.8 36.0 19.8 18.0 --
Non-Inductive
Amperes
16.0 9.2 8.0 7.2 -- -- 6.0 6.0 6.0 6.0
Pilot Duty (for both
sets of contacts)
125 VA at 24 to 600 VAC; 57.5 VA at 120 to 300 VDC
* Not for compressor motor loads
P70, P72, and P170 Series Controls for Low Pressure Applications Installation Instructions 7